Hansen APP08 Скачать руководство пользователя страница 5

5

APP-001b

APR 2007

WATER BUBBLER DRAIN LINE

A 1” (25 mm) PVC socket/1” FPT water drain connection 

is located at the bottom of the bubbler. The water bubbler 

drain line should flow to a suitable drain or container. See 
Figure 4. If the drain line is run overhead, the fitting on the 
top of the water bubbler must be sealed, including the ¼” 
NPT vent connection in the fitting, and a protective mesh 

installed around the clear tube. Do not run the line more 
than 10’ (3 m) above the height of the bubbler because the 
pressure on the water bubbler could be excessive. Support 
the drain line to prevent undue stress on the water bubbler. 

Also, do not install a shutoff valve in this line. 

Initially, fill the water bubbler with water through the 3” 
(80 mm) plug located on top of the tube. Keep the plug 
lubricated and hand tight. Check for leaks at the hose 
fittings.

WATER PURGE LINE

Water removed from the refrigeration system by the 

AUTO-PURGER Plus flows out the water purge line.  This 

line should be directed to a customer supplied container, 

such as a 55 gallon drum for example. See Figure 4. It is 
recommended to use rigid metal tubing or to secure the 

line.  Commonly, when draining water initially all the water 
is released, then any oil is released, and then a small 

quantity of ammonia vapor may be released.  A loose hose 
may whip around when the last of the liquid slugs come 
out of the hose and is therefore not recommended.  The 
customer supplied container may be par tially filled with 
water, and the end of the water purge line submerged in 
this water so that any small amount of ammonia vapor 
that may be released is dissolved in this water.

OIL DRAINS

Excess oil can reduce the purger capacity by lowering 
the evaporating or condensing rate. Oil is not typically a 
problem. Oil in the evaporator chamber is typically released 
with the water that is released out the water purge line.  
However, any oil that may collect in the purger can be 
drained off through the two capped ¼” valves on the purger. 
See Figure 1. Before draining oil, close the foul gas and 
low-pressure pumped-liquid valves. Allow the purger to 
pump out, then close the low-pressure liquid return and 
suction line valves. Use normal oil draining precautions 
to prevent injur y or proper ty damage.

ELECTRICAL CONNECTIONS

The standard AUTO-PURGER Plus requires a 115V 50/60Hz 
17 amp electrical supply on a 20 amp circuit breaker; 

models for 220V 50/60Hz, 11 amps electrical supply on 
a 15 amp circuit breaker are available. All models have a 

½” (13 mm) knockout on the side of the control cabinet to 

access the power connection terminal strip. Any unused 

knockout holes must be sealed to prevent splashing water, 

dust, and debris from entering the control cabinet. After 
completing all electrical connections inside the cabinet, 
connect the cable from the PLC Control Console to the 
PLC. Connect the cable plug to the socket and tighten the 

hand screws. Refer to the wiring tag inside unit.

AUTO-PURGER Plus models APP08, APP16, and APP24 

have an additional ¾” (20 mm) knockout for individual 
purge point solenoid valves. Wires from each purge point 

solenoid valve should be brought to the purger control 
cabinet. Any additional access holes should be made on 
the side of the control cabinet. All access holes into the 
control cabinet must be sealed to prevent moisture, dust, 
and debris entering the cabinet.

From each purge point solenoid, one wire is connected 
to the corresponding screw terminal for the purge point 
inside the control cabinet on the terminal strip.  For 115VAC 
models, the other wire from the purge point solenoid is 
connected together for all the purge points and tied to the 
available neutral position on the top terminal strip.  For 
the 220VAC models, the other wire from the purge point 
solenoid is connected together for all the purge points 
and tied to the top terminal strip labeled PP_COM.

Models APP08, APP16, and APP24 supply 115VAC to the 
purge points regardless of whether 115VAC or 220VAC is 
supplied to the control cabinet.

All APP models have a relay available which energizes 

whenever  action  is  required  by  plant  personnel.    The 
normally open contacts will close when action is required.  
If desired, the contacts may be connected to a light, an 
audible alarm, or to a plant computer, to notify plant 
personnel to attend to the purger.  The contacts are rated 
for 10 amps.  Connection to the relay is made at the top 
terminal strip labeled REMOTE REL AY.

LEAK TEST

Use standard refrigeration procedures to check the 

AUTO-PURGER Plus for leaks before placing it in service. 

To confirm a leak-free AUTO-PURGER Plus, manually 

open  one  remote  purge  point  solenoid  valve,  if  there  is 
one. Manually open the foul gas shut-off valve and allow 
pressure inside the purger to build to condensing pressure, 
as shown on the high side pressure gauge. Then, manually 
open the high side to low side bypass valve to pressurize 
the evaporator section of the purger, as shown on the low 
side pressure gauge. See Figure 4. Check for leaks. Close 
the high side to low side bypass valve.

Содержание APP08

Страница 1: ...RGER Plus is a totally automatic electronically controlled refrigerant noncondensible gas air and water purger for reducing the energy costs of operating an ammonia refrigeration system All models are...

Страница 2: ...circumstances only one point is effectively purged The best practice is to purge each condenser and receiver circuit separately It is extremely important to install purge points at locations sure to b...

Страница 3: ...some cases a small high pressure auxiliary receiver is located at the outlet of one or more condensers This receiver should have a purge point at the top Where a high pressure float regulator is used...

Страница 4: ...ected into the purger The low pressure pumped liquid line feeds makeup liquid as required during purging The line contains liquid ammonia that typically is also contaminated with water which is to be...

Страница 5: ...mps electrical supply on a 15 amp circuit breaker are available All models have a 13 mm knockout on the side of the control cabinet to access the power connection terminal strip Any unused knockout ho...

Страница 6: ...connecting shut off valves are open See Figure 4 START UP Make sure all piping electrical connections and settings are complete as described in this bulletin Open the foul gas low pressure pumped liq...

Страница 7: ...there are no releases to atmosphere 1 WATER BUBBLER WATER BUBBLER OVERFLOW TUBE FOUL GAS LINE LOW PRESSURE PUMPED LIQUID LINE SUCTION LINE FILL LINE D B C FLOW REGULATOR GAUGE VALVE GAUGE VALVE LIQUI...

Страница 8: ...system parameters The operator can switch between the two message types by pressing the esc key Control Console Specifications Display Type Character LCD 4 lines by 20 characters w LED backlight Encl...

Страница 9: ...and the temperature of the plate heaters see figure 4 Another press of this key displays the pressures in the low side and the high side of the purger A final press of this key returns the display to...

Страница 10: ...follows air purge limit 60 minute limit normal 0 60 min startup 1 nolimit purge point enable 01 1 enable 0 skip 02 1 enable 0 skip 03 1 enable 0 skip 04 1 enable 0 skip 05 1 enable 0 skip 06 1 enable...

Страница 11: ...normal 7777 loss of lp liq will appear when the liquid make up solenoid valve has been energized for 30 minutes continuously ERROR HEATER FAULT will be displayed if the heaters are on longer than 4 ho...

Страница 12: ...1 psid 07 bar check valve in the water purge line to prevent reverse flow of water into the purger from the customer supplied container The water bubbler fill line has a check valve OPERATION OF PURG...

Страница 13: ...URGE GAS GAUGE VALVE WIDE OPEN DURING OPERATION CLOSED FOR SERVICING PURGER PURGE GAS 1 32 0 8 MM DIA METERING ORIFICE 0 07 BAR PURGE GAS TO WATER BUBBLER OR TO CUSTOMER SUPPLIED WATER BOTTLE CHECK VA...

Страница 14: ...r fill line valve The purger will pump down in several hours To accelerate the process attach ammonia hoses to the oil drain valves and pump out into a suction line Close the low pressure liquid retur...

Страница 15: ...por Trap H5600R Relief Valve 300 psi ELECTRICAL 70 1088 Solenoid Coil DIN plug 115V 50 60 Hz 16 Watt 20 2428 Electric Heater 115V 50 60 Hz 750 Watt 20 2477 Electric Heater 230V 50 60 Hz 750 Watt 20 12...

Страница 16: ...ctional pushbutton several times until the pressures are displayed Verify that the high side pressure is greater than 80 psig 5 5 barg Action If the high side pressure displayed is less than 80 psig 5...

Страница 17: ...id line plugged strainers or the plastic shipping cap still in the liquid line flange Action Inspect piping for a closed shut off valve Open the shut off valves clean the strainer or remove the shippi...

Страница 18: ...18 APP 001b APR 2007 THIS PAGE INTENTIONALLY BLANK...

Страница 19: ...ce schedule and the Safety Precautions Sheet supplied with this product Escaping refrigerant can cause injury especially to the eyes and lungs WARRANTY All Hansen products except electronics are guara...

Страница 20: ...poration 6827 High Grove Boulevard Burr Ridge Illinois 60527 USA Tel 630 325 1565 Fax 630 325 1572 Toll 800 426 7368 Email info hantech com Web www hantech com USA Asia Europe India Latin America Midd...

Отзывы: