General Valve Installation Procedure
Note:
Install the softener with the inlet, outlet, and drain connections according to manufacturer recommendations and meeting all applicable plumbing codes.
1. Install the softener tank as close as possible to a drain while maintaining convenience. The installation location should be on a stable
and level surface.
2. All plumbing functions must adhere to local, state, and federal plumbing codes.
A 1/2” minimum drain pipe should be used.
A 3/4” drain pipe should be used in applications where backwash flow rates exceed 7gpm or length exceeds 20 feet. There must be an
air gap between the drain line and the drain to prevent siphoning of contaminated water back into the resin tank. (Figure 1-1)
3. The
1” distributor tube should be cut so it is flush with top of tank.
4. Pre-lubricate the distributor o-ring seal and tank o-ring seal. Twist the valve on to the tank. Silicone lubricant is the only lubrication
recommended.
5. Teflon tape should be used for the drain fitting. Solder joints should be completed prior to connecting piping to the
valve. 6” of clearance
(152mm) minimum between the valve and solder joints are required while soldering pipes that are connected to the valve. The valve
manufacturer is not responsible for damage incurred during installation.
6. When placing the brine tank, the surface must be stable and level.
7. Fill brine tank until
the water is 1” (25mm) above the grid plate. If a grid plate is not used, fill with water until it is above the air check on float.
Do not add salt at this time.
8. If the unit is installed with a bypass, switch to bypass function. Open the main water supply. Turn on a downstream cold water faucet
nearby and run water for several minutes or until the water runs clean.
9. Turn the bypass valve to the
“In Service” position and allow water to flow into the resin tank. After the water stops flowing into the
tank; air should be purged from the system. Open a cold water faucet and let water run until air is purged, then turn it off.
10. Connect unit to an approved power source only. Preferably a GFI and grounded outlet.
Craft