INSTALLATION INSTRUCTIONS

69-2496-03

WV4262B Powered Damper 
Water Heater Controls

APPLICATION

The WV4262B Water Heater Control System is 
designed for power damper water heater applications.

The WV4262B provides these features:

• Gas regulation and manual valve features

• Intermittent spark-to-pilot ignition

• Flame supervision using flame rectification 

sensing through the spark rod. This flame sense 
circuit uses patented technology to create a 
robust sensing signal that is independent of AC 
line polarity and appliance earth grounding.

• Water temperature sensing using solid state 

sensors potted in a submersion well assembly

• Manually resettable High Temperature Cutout 

(TCO)

• Damper motor control with position sensing

• Variable resistance flammable vapor sensor with 

a sensing and control algorithm to provide 
automatic shutdown when hydrocarbon vapors 
such as gasoline are detected

• Retains up to 10 fault code histories in non-

volatile memory (available through the 
EnviraCOM™ communication port)

• Solid state setpoint adjustment over a factory 

preset temperature range using a linear 
potentiometer to provide high resolution 
adjustment

Special control features are available to address 
items such as stacking. See a Honeywell Product 
Specialist for more information.

The specific application of the WV4262B System is 
the responsibility of the appliance manufacturer. See 
the Specifications below for temperature ranges and 
regulator types. The WV4262B system refers to the 
combination of the valve and the electronic control 
module.

SPECIFICATIONS

IMPORTANT

WV4262B

 Controls provide direct replace-

ment only; do not substitute other models.

Body Pattern:  

90 degree with 1/2 in. inlet and 1/2 in. 

inverted flare outlet.
Natural gas model has right-hand threaded 

inverted outlet.

LP gas model has left-hand threaded inverted out-

let.

Mounting:  

Mounting in upright position only.

Electrical Tolerences:

Voltage Minimum: 18 VAC RMS, 60 Hz.
Voltage Maximum: 30 VAC RMS, 60 Hz.
Current in Running Mode: 0.3 Amps @ 24 VAC (plus 

inducer motor draw)

Current in Idle Mode: 0.3 Amps Max @ 24 VAC
Damper Relay: 24 VAC RMS, 1 Amp Switching Cur-

rent. 75,000 Cycles Life @ max load.

Capacity: 

See Table 1.

Conversion: 

Use conversion factors in Table 2 to 

convert capacities for other gases.

Regulation Range (Btuh);

With 1/2 in. NPT inlet and 1/2 in. Inverted Flare Out-

let:

Natural Gas:

Minimum: 30,000
Maximum: 100,000

LP Gas:

Minimum: 40,000.
Maximum: 100,000

Inlet Pressure Range:

See appliance rating plate for Inlet Pressure range 

recommendation

1/2 PSI (14.0" w. c.) maximum inlet pressure allowed 

for proper operation.

Operational Environment:

Operating Ambient Temperature Range:

32 °F to 150 °F (0 °C to 65 °C)*

Shipping and Storage Temperature Range

 -20 °F to 120 °F (-29 °C to 49 °C)

* Gas valve regulation range is guaranteed from 32 °F 

to 150 °F (0 °C to 66 °C)

Содержание WV4262B

Страница 1: ... the WV4262B System is the responsibility of the appliance manufacturer See the Specifications below for temperature ranges and regulator types The WV4262B system refers to the combination of the valve and the electronic control module SPECIFICATIONS IMPORTANT WV4262B Controls provide direct replace ment only do not substitute other models Body Pattern 90 degree with 1 2 in inlet and 1 2 in invert...

Страница 2: ...r See Honeywell product specialist for other available accessories Table 1 Capacity of WV4262B a Capacity based on 1000 Btu ft3 0 64 specific gravity natural gas at 1 47 in wc pressure drop 37 3 MJ meter3 0 64 specific gravity natural gas at 0 37 kPa pressure drop b Valves are guaranteed at only 77 percent of the rating Fig 1 Typical capacity curve for WV4262B Family Water Heater Control System Ta...

Страница 3: ... the control to fail Never install an appliance where water can drip on the control In addition high ambient humidity can cause the control to corrode and fail If the appliance is in a humid atmosphere make sure air circulation around the control is adequate to prevent condensation Also regularly check out the system Corrosive Chemicals Corrosive chemicals can attack the control eventually causing...

Страница 4: ...h Always use a direct replacement sensor assembly when replacing the temperature sensor WARNING Electrical Shock Hazard Can cause severe injury death or property damage Disconnect power supply before making wiring connections to prevent electrical shock or equipment damage Location The WV4262B is mounted on the outside of the water heater tank See Fig 3 Install Control to Water Tank 1 To install t...

Страница 5: ... sure the ends are square deburred and clean All tubing bends must be smooth and without deformation 3 Run pipe or tubing to the water heater control If tubing is used obtain a tube to pipe coupling to connect the tubing to the control 4 Install a sediment trap in the supply line to the water heater control See Fig 4 Table 3 NPT Pipe Thread Length in Fig 4 Install a sediment trap in the supply lin...

Страница 6: ...the burner Turn on Main Burner CAUTION Dry Tank Hazard Can cause the device to malfunction The tank must have water in it before turning on the control Follow the instructions provided by the appliance manufacturer or turn the Control s ON OFF switch to the ON position then adjust the temperature using the setpoint knob WARNING Scalding Hazard Can cause burns severe injury or death Never move setp...

Страница 7: ...uge Also move the manual gas shutoff switch to the OFF position when removing the gauge and replacing the plug Repeat Gas Leak Test at plug with main burner operating Refer to the OS label on the Control for the pressure reading which should match the manometer reading Gas Input and Burner Ignition Check and Adjustment 1 Check the full rate manifold pressure listed on the appliance nameplate Water...

Страница 8: ...NG Fire or Explosion Hazard Can cause severe injury death or property damage Do not disassemble the water heater control it contains no replaceable components Attempted disassembly or repair can damage the control Sequence of Operations 1 Follow the sequence of operation as shown in Table 4 Table 4 WV4262B Sequence of Operation Sequence Mode Description Power Up 1 Start up Upon Power up the contro...

Страница 9: ...or The damper motor is de energized Sequence Mode Description Green LED Status Indicates Check Repair Short flash once every four seconds Idle no call for heat and no faults Not Applicable Heartbeat alternates bright dim Call For Heat no faults Not Applicable Short flash once per second Idle mode Low Flame Signal on last call for heat Check spark flame sense rod for build up of silicone dioxide Ch...

Страница 10: ...e vapors were detected at potentially explosive levels Verify no gasoline vapors are still present To reset the control cycle power to the appliance via the ON OFF switch or power cord and within 30 seconds cross the HOT set point twice with the set point knob Replace the Flammable Vapor Sensor element if a gasoline spill event occurred Eight One Flash three second pause FVS Fault Detected Verify ...

Страница 11: ... AND DAMPER END SWITCH PILOT VALVE SHOULD OPEN AND IGNITION SOURCE SHOULD START SPARKING UNTIL PILOT FLAME IS LIT YES NO YES NO YES NO YES NO CHECK INLET PRESSURE MAKE SURE AIR IS BLED OUT OF SYSTEM CLOGGED PILOT ORIFICE GAS LEAK IN PILOT TUBING CONNECTIONS WIRING TO THE FLAME SPARK ELECTRODE FLAME SPARK ELECTRODE IS IN THE CORRECT POSITION RELATIVE TO THE PILOT BURNER CHECK DAMPER END SWITCH INCL...

Страница 12: ... outlined by the manufacturer of your appli ance can differ requiring special instructions WARNING Electrical Shock Hazard Can cause severe injury death or property damage Disconnect power supply before making wiring connections to prevent electrical shock or equipment damage STOP READ THE WARNINGS TURNING ON THE APPLIANCE If the appliance does not turn on when the setpoint knob is set several deg...