HANBELL COMPRESSOR
INSTALLATION & START-UP GUIDE
RC2-100 TO RC2-930
Rev M.5.2
WARNING!
NO OIL
is shipped in compressor.
Compressor must
NEVER
be run backwards.
These Safeties ARE Required at Startup to Maintain Hanbell Warranty
a) Motor Module Trip (INT69HBY): Open for 1 second
b)
Low Oil Level Float Trip: Open for 30-60 seconds
c)
Unsafe Suction: Less than 5 psi for 3 seconds
d)
Low Differential Pressure: Less than 65 psi for 60 seconds (Oil Psi – Suction Psi)
e)
Unsafe Differential Pressure: Less than 35 psi for 5 seconds (Oil Psi – Suction Psi)
f)
Low Discharge Superheat: Less than 25°F for 300 seconds