COMPRESSOR INSTALLATION & START-UP GUIDE
REVISION M
12. Hanbell with VFD
12.1.
Wiring & Controls Set Up
•
For a new installation
,
DO NOT CONNECT
the L1, L2, and L3 Red, White and Blue wires to the INT69HBY
motor module.
•
For an existing installed compressor REMOVE
the red, white and Blue wires from the INT69HBY motor
module.
•
Place the amp sensor(s) on the line side of the VFD.
•
Select only a constant torque VFD type to use.
•
Set for no Direct Current (DC) braking
•
Set Acceleration Time to 3-5 second
12.2. Compressor Set Up
•
Remove the 50% load solenoid coil (50% is no longer used).
•
The 25% load solenoid is used as the Fast Unload.
•
Remove the Load solenoid stem and install a Load Cap in its place.
Final Configuration
50%
75%
LOAD
25%