HAMWORTHY HEATING LTD
28
WESSEX 100 M
500001080/F
Gas pressure switch setting:
Natural gas = 14mbar
Propane = 25mbar
Operational check of gas pressure switch.
1) Connect manometer to pressure tapping.
2) Close the gas service valve to lock up mains
pressure. Reduce pressure by loosening inlet
test point or the gas control valve until the
desired pressure is achieved.
3) Determine operation of switch using a suitable
multi-meter.
Figure 14.10 Gas Pressure Switch Adjustment
SCREW M4x6 POZI PAN
NYLOCK NUT M3
EYELET
Содержание Wessex 100 M100