HAMWORTHY HEATING LTD
21
WESSEX 100 M
500001080/F
Figure 12.2a Fault Finding Procedures
Initial Start Procedure
Is the fan running ?
Yes
Continued
Ref Fig 12.2b
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
No
No
No
No
No
No
No
No
No
Is mains power on ?
Has the ignition
controller reset ?
Has the air pressure
switch proved ?
Is there a glow at the HSI
probe ?
Is the temperature limiter
reset ? (Indicated on the
fascia as Overheat)
Is there a demand from the
thermostat ?
Is remote control link
(C1-C2) secure ?
Is there power at the
ignition controller ?
Is 'Fan On' neon
illuminated on fascia ?
Replace ignition
controller
Check fuse(s) time clock
etc.
Re-set ignition
controller (Lockout
button on fascia).
Check thermostats.
Check air sensing venturi
and pressure switch
connecting tubes.
Check that the probe and
electrode connections are
secure and sound.
Re-set temperature
limiter (Limit Stat)
Check and turn
thermostat to maximum.
Check and close
remote circuit.
Check wiring
Check fan motor and
air pressure switches
No
Yes