Figure 12.2b Fault Finding Procedures (Cont.)
Does the gas valve operate,
lighting the burner ?
Yes
Yes
No
No
No
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
No
Continued from
Fig 12.2a
No
No
No
No
No
No
Is the flame signal from the
probe above the minimum
(0.7uA) ?
Is there power at the
gas valve ?
Replace the gas valve
Does the boiler operate at
High fire ?
Is the High/Low link across
terminals (C3 - C4) ?
Is there power at the gas
valve High fire solenoid ?
Does the damper blade
move to the High fire
Replace the gas valve
Does the boiler
operate at Low fire ?
Does the boiler cycle
On/Off rapidly ?
The boiler is operating
correctly.
Thermostat faulty. Poor
circulation due to air in
system or faulty pump
Check setting of High/Low
thermostats. Check damper
operation.
Poor circulation due to air
in system or faulty pump
Poor circulation. Thermostat
set too high or faulty. Boiler
waterways scaled up. Gas
pressure incorrect. Check
gas setting pressure
Does the boiler overheat
and the system remain
Boiler noisey
Check the probe wiring
Check the gas valve
plug and wiring
Check C3 & C4 terminal
wiring. Check B.E.M.S
load requirements
Check gas valve plug and
wiring. Check pressure
switches. Check timer
delay relay on pcb.
Check that the damper
blade is free. Check
solenoid coil