80-150 kW Frame & Header Kits Manual
3 MULTIPLE BOILER SYSTEM COMPONENTS
3.1 GENERAL
The multiple boiler systems consist of the following components:
•
Pipekit (1 and 2 wide configurations)
•
Boiler gas header.
•
Boiler flow and return headers supported on mounting skid
•
Low loss mixing header (optional)
•
Hardware pack (includes essential connection and valve components)
•
Circuit extension kits (optional)
•
Plate Heat exchanger kit (optional)
•
Boiler pump
3.2 MAIN WATER HEADERS
The main water headers consist of: water flow, water return headers custom sized for all boilers. It is possible to extend the system to a
maximum of 6 boilers in a linear configuration.
Each header kit provides water flow and return headers sized either DN80 or DN100 dependent on total maximum combined heating
output required.
3.3 GAS HEADER
The Gas header consists of a custom manufactured 2” manifold. This is located in a cradle incorporated within the header mounting skid.
3.4 BOILER PUMP
Pump kits and External pump controls
(sold separately)
are designed to provide the optimum flow around the appliance water circuit
ensuring the maximum flow rates are contained within the design constrains of the appliance.
Содержание Stratton mk3