![Hamworthy Stratton mk3 Скачать руководство пользователя страница 3](http://html1.mh-extra.com/html/hamworthy/stratton-mk3/stratton-mk3_manual_3494096003.webp)
3
80-150 kW Frame & Header Kits Manual
1 INTRODUCTION
This technical data contains information for dimensioning & assembly
of a cascade system kit for the Stratton mk3.
Frame and header kits are available 'in line' configurations only.
GENERAL DESCRIPTION OF FRAME & HEADER KITS
A requirement to spread the total required heat output over several
boilers can be accommodated by the use of the Hamworthy multiple
boiler frame & header kit options.
All headers and pipe work should be insulated in accordance
with the Non Domestic Building Services Compliance Guide. To
ensure compliance with the maximum heat loss criteria, insulation
thickness should be calculated according to BS EN ISO 12241 using
standardised assumptions.
2.1 FRAME AND HEADER KIT DESIGN OPTIONS
The Stratton mk3 boilers are suitable for use in a multiple boiler configuration. The Stratton mk3 multiple boiler system is
available in side by side and giving the opportunity to choose the optimum footprint size or wall space for a given output. 80-150
kW kits include the support frame. Boilers can be wall mounted required.
2 GENERAL DESCRIPTION OF SYSTEMS
continued . . . . .
Available Rig Configurations
Total Output
Required kW
Number of boilers
and Frames
Footprint Size
W x D x H (mm)
Frame and Header
Kit
Range
Size
Prod. No
Single Frame Configurations
80-120
1
500 x 704 x 1535
DN80
232865
Twin Frame Configurations
160-240
2
1000 x 704 x 1535
DN80
232866
Triple Frame Configurations
240-360
3
1500 x 704 x 1535
DN80
232867
Quad Frame Configurations
320-480
4
2000 x 704 x 1535
DN80
232868
Five Frame Configurations
400-600
5
2500 x 704 x 1535
DN80
232869
Six Frame Configurations
480-600
6*
3000 x 704 x 1535
DN80
232870
Available Rig Configurations
Total Output
Required kW
No of boilers
and Frames
Footprint Size
W x D x H (mm)
Size
Frame and
Header Kit
Range
No sep/
LLH
PHEX
sep
Single Frame Configurations
150
1
500 x 794 x 1830
DN100 235371
232871
Twin Frame Configurations
300
2
1000 x 794 x 1830
DN100 235372
232872
Triple Frame Configurations
450
3
1500 x 794 x 1830
DN100 235373
232873
Quad Frame Configurations
600
4
2000 x 794 x 1830
DN100 235374
232874
Five Frame Configurations
750
5
2500 x 794 x 1830
DN100 235375
232898
Six Frame Configurations
900
6
3000 x 794 x 1830
DN100 235376
232899
Note.
All boilers need to be sized in accordance to the total required heat load and the modulation capabilities of the appliances.
* Max 6 x 100 kW only.
H
=Height from floor to top of frame,
D
=Depth from installed wall to front of kit,
W
=Width of installed kit
DN80
DN100
232876
232877
kW
Product No.
Stratton mk3 80
AA082638
Stratton mk3 100
AA082639
Stratton mk3 120
AA082640
Stratton mk3 150
AA082641
Table 1 80-120 kW
Table 2 150 kW only
Table 3 Available Stratton mk3 Boilers
Table 4 Low Loss Header Accessories