5. When you no longer need to control the fire damper manually, remember to release the status of the fire
damper.
a. On the row of the fire damper, select the "Control" column.
b. In the selection window, select "Auto".
After a while, you can see in the Dampers view that the status of the fire damper has changed.
If you get errors when doing the task, see
.
7.3.8 Changing the time and date
Here you change the time and date of the system. You can also change the time zone or modify other clock-related
settings.
For instructions, see
.
7.3.9 Updating the version of a Halton Safe HSL link unit
Here you update the software of a Halton Safe HSL link unit.
1. Log in as Installer. For instructions, see
.
2. In the upper left corner of the view, from the drop-down list, select "Programming".
3. From the lower drop-down list, select "Module versions".
The link units and their current software versions are listed in the upper table. The available versions are
listed in the lower table.
Halton Safe Management 2.0 (SM2) - Installation, commissioning, operating, and maintenance guide
59