![Halton EcoloAir 10000CFM Скачать руководство пользователя страница 20](http://html1.mh-extra.com/html/halton/ecoloair-10000cfm/ecoloair-10000cfm_operators-manual_581583020.webp)
20
EcoloAir Operation, Maintenance & Service Manual
EA
OMSI/0
1
2
0
09/re
v1/EN
1.17 Momentarily energize the fan to check the direction of rotation. Listen as the fan coasts to a
stop for any unusual noise, identify the source, and take corrective action as necessary.
1.18 Switch on the electrical supply and allow the fan to reach full speed. Check carefully for:
a) Excessive vibration
b) Unusual noise
c) Proper belt alignment
d) Proper lubrication
e) Proper amperage, voltage, or power values.
f) If any problem is indicated, SWITCH OFF IMMEDIATELY.
g) Lock out the power supply. Secure the fan impeller if there is a potential for wind milling.
Check carefully for the cause of the trouble, correct as necessary, and repeat check list
procedure.
2.0 Even if the fan appears to be operating satisfactorily, shut down after a brief period, lock out the
power supply, and recheck item 1.5 through 1.17 as the initial start-up may have loosened the
bolts, fasteners, and set screws.
3.0 The fan may now be put into operation, but during the first eight (8) hours of running, it should be
closely observed and checked for excessive vibration and noise. At this time checks should also
be made of motor input current and motor and bearing temperatures to ensure that they do not
exceed manufacturer’s recommendations.
4.0 After eight (8) hours of operation, the fan should be shut down and the power locked out. Check
list items 1.5 through 1.17 should be inspected and adjusted, if necessary.
5.0 After twenty-four (24) hours of satisfactory operation, the fan should be shut down (locked out)
and the drive belt tension should be readjusted to recommended tension.
6.0 After commissioning and start-up, the fan should be operated and maintained in accordance with
the manufacturer’s and component manufacturer’s recommendations.
For any questions, please call Halton Service Network at (905) 624-301.
START UP CHECK LIST Continued...