EcoloAir Operation, Maintenance & Service Manual
EA
OMSI/0
1
2
0
09/re
v1/EN
TROUBLESHOTING GUIDE
PROBLEM
PROBABLE CAUSE
SOLUTION
Filter alarms triggering
a) Plugged fi lter.
b) Broken pressure switch air
tube.
c) Loose pressure switch fi tting.
d) Condensation in pressure
switch tubing.
a) Check fi lter. Replace if required
What setting did it alarm at?
Adjust pressure switch if
required.
b) Repair break. Check for cause
of break.
c) Tighten fi tting.
d) Blow out condensation from
air tube. For outdoor installation
check to see if heat wire is
installed and operating. If not
installed, recommend to the
owner that it be installed.
Unit starts, then shuts down a) Filter not seated properly
b) Broken or loose pressure
switch air tube.
c) Exhaust fan belt slipping (not
moving enough air).
d) Timer not set correctly.
e) Defective timer.
f) Off on overload heaters.
g) Overall pressure switch #4 not
set properly.
a) Seat fi lters.
b) Repair break or tighten fi tting.
c) Tighten or replace fan belts.
d) Set time for 60 seconds.
e) Replace timer. If burnt out it
will have burn mark on top
right side.
f) Check, reset and check
amperage draw.
g) Adjust pressure switch setting.
No odor control and/or
spraying action
a) No power to compressor
b) No fl uid from nozzle.
c) Compressor too hot.
d) Supply tube not connected/
loose or cracked.
a) Check power to Compressor.
b) Check condition of orifi ce,
check condition of liquid supply
line at foot valve.
c) Check amperage, verify spray
time setting. Check for adequate
venting.
d) Re-connect tube or replace.