EcoloAir Operation, Maintenance & Service Manual
EA
OMSI/0
1
2
0
09/re
v1/EN
START UP OPERATING INSTRUCTIONS
IMPORTANT: Initial system start-up and certifi cation by factory authorized personnel only.
Operating system prior to certifi cation will void warranty.
• Turn on main disconnect switch at EcoloAir fan.
• The EcoloAir fi lter unit is designed to operate with the following pressure drops across each fi lter
stage.
1)
Pre
Filter
.2”
to
.75”
2)
Medium
Effi ciency Filter
.4” to 1.25”
3)
High
Effi ciency Filter
.75” to 2.0”
When the pressure drop for each fi lter bank exceeds the upper limits, an audible/visual alarm will
sound and activate a pilot light.
The alarm is a warning only, and does not shut the system down. The alarm can be silenced by
pushing the alarm reset button in the centre of the Ecology panel.
• There are two other alarm conditions:
1)
“A
fi lter not in place” sensing system. 2) A fi re state to sense excessive temperatures in the
duct. Should either alarm be triggered, the audible/visual alarm will sound, an indicator light
labeled “fi lters overall” will be illuminated, and the system will shut down. After the cause
of the alarm has been corrected, the system can be restarted by pushing the reset button
and also turning the main disconnect switch to the “OFF” position. then back to the “ON”
position.
MAINTENANCE INSTRUCTIONS
NOTE: Heavy hamburger type operations require extra maintenance and frequent fi lter changes. We
recommend a maintenance contract be set up for this type of operation.
MONTHLY:
• Check condition of air filters. Replace if necessary.
• Check odor control liquid level. Replace if necessary.
• Check odor nozzle condition (check for debris)
QUARTERLY: (to be performed by a qualified service agent).
• Check belt tension at exhaust fan. Tighten as required.
• Check belt alignment.
• Lubricate motor bearings.
• Lubricate fan bearings.
• Check contacts on motor starter in control panel.
• Check amperage draw of fan motor.
• Check to see if the overall filter warning system operates correctly. This can be done by removing
the high efficiency filters and starting the system.
• Check fusible link on the fire dampers (filter section)
When replacing belts when multiple belts are used, they MUST ALL BE REPLACED, as they are a
matched set.