PRESSURE CONTROLLER operating manual
13
Power and Signal Connections
Power can be supplied to your controller through either the power jack or
the multi-pin connector on top of your device, depending on configuration.
✓
Note:
Controller power jacks require a 12–30 Vdc power supply
with a 2.1 mm female positive-center plug capable of supplying
at least 250 mA, with an additional 40 mA for a color display.
4–20 mA analog outputs require at least 15 Vdc and 290 mA.
✓
Note:
Large valve controllers (PCR models) require a
24–30 Vdc power supply with a 2.1 mm female positive-
center plug capable of supplying at least 750 mA.
Standard 8-Pin Mini-DIN Pinout
For 6-pin locking industrial connector, M12, DB9, and DB15 pinouts, see
or visit
.
Pin Cable Color Function
1
Black
Not connected
Optional: 4–20 mA primary output signal
2
Brown
Static 5.12 Vdc
Optional: Secondary analog output
(4–20 mA, 0–5 Vdc, 1–5 Vdc, 0–10 Vdc) or basic alarm
3
Red
Serial RS-232RX input signal
Optional: RS-485 A
4
Orange
Analog setpoint input
5
Yellow
Serial RS-232TX output signal
Optional: RS-485 B
6
Green
0–5 Vdc
Optional: 1–5 Vdc or 0–10 Vdc) output signal
7
Blue
Power in (as described above in the checked notes)
8
Purple
Ground (common for power, digital communications,
analog signals, and alarms)
▲
Caution:
Do not connect power to pins 1 through 6
. Permanent
damage can occur. Pin 2 (5.12 Vdc Output) is often mistaken
for the standard 0–5 Vdc analog output signal. Pin 2 is
normally a constant 5.12 Vdc that reflects system bus voltage.