APPENDIX A - SETTINGS
37
Figure 5 – Factory Supplied Air Handler Control Board
Factory Supplied Air Handler TXV Kit Installation Instructions:
1.
Ensure the coil has not been exposed to atmospheric pressure for more than 15 minutes.
2.
Remove indoor air handler coil inlet cover at the distributor body inlet. Use a back-up wrench to prevent damage to the copper
lines connected to already and being connected to the TXV.
3.
Install the TXV on the distributor using a back-up wrench to prevent damage to the copper lines connected to already and being
connected to the TXV. Tighten finger tight, then ¼ turn more.
4.
Connect the equalizer tube of the TXV to ¼” equalizer fitting on the vapor line. Be sure to remove the Schrader Valve Core
located in the fitting on the coil.
5.
Install the indoor air handler coil 3/8” liquid line tube. Use back-up wrench to prevent damage to the copper lines connected to
already and being connected to the TXV.
6.
Attach the TXV bulb to the horizontal section of the suction line using the bulb strap and insulation that is in the kit package. As
always with TXVs, the bulb should be installed between 10 o’clock and 2 o’clock on the pipe.
7.
Refer to the indoor air handler unit installation manual for further installation of the indoor air handler unit.
Содержание Acadia i Series
Страница 44: ...APPENDIX B WIRING DIAGRAMS 43 Figure 8 Line Voltage Wiring...
Страница 45: ...APPENDIX B WIRING DIAGRAMS 44 Figure 9 Hallowell Controller Wiring...
Страница 47: ...APPENDIX B WIRING DIAGRAMS 46 Figure 12 Entire Low Voltage Wiring with Electric Back Up...
Страница 48: ...APPENDIX B WIRING DIAGRAMS 47 Figure 13 Entire Low Voltage Wiring with Dual Fuel Back Up...
Страница 54: ...APPENDIX D ACADIA OUTDOOR UNIT MOUNTING 53 Figure 15 Typical Acadia Mounting...
Страница 56: ...APPENDIX E ACADIA COMPONENTS 55 Figure 17 Acadia Components...
Страница 57: ...APPENDIX F EWC ZONE CONTROL 56 Figure 18 Acadia with EWC Zone Control Wiring...