INSTALLATION STEPS
15
(NOTE)
The minimum outdoor operating ambient in the cooling is 50°F (10°C) and the maximum outdoor ambient in cooling is
125°F (51.7°C). The minimum outdoor operating ambient in heating mode is -30°F (-34.4°C) and the maximum outdoor ambient
in heating is 82°F (27.8°C).
To prevent personal injuries, wear safety glasses, protective clothing, and gloves when handling refrigerant and observe the
following:
(CAUTION)
Use only R-410A rated refrigerant equipment.
IMPORTANT:
Keep the equipment and manifold hoses clear of debris and moisture.
IMPORTANT:
Do not vent refrigerant to the atmosphere. Recover refrigerant before system repairs or final unit disposal.
(CAUTION)
If there is ever a question of how much charge has been introduced into the system while charging, recover and re-
charge the system. Record the amount of final charge with a permanent marker on the service sticker where it will be clearly
visible.
Hallowell Line Set Charging Chart
Line Set Length
Acadia 024
Acadia 036 & 048
Line Set Length
Acadia 024
Acadia 036 & 048
(ft)
(m)
lb - oz
kg
lb - oz
kg
(ft)
(m)
lb - oz
kg
lb - oz
kg
0-10
0-3.04
9 - 0
4.08
12 - 8.0
5.67
11
3.35
9 - 0.6
4.10
12 - 8.6
5.69
31
9.45
9 - 12.6 4.44
13 - 4.6
6.03
12
3.66
9 - 1.2
4.12
12 - 9.2
5.70
32
9.75
9 - 13.2 4.46
13 - 5.2
6.04
13
3.96
9 - 1.8
4.13
12 - 9.8
5.72
33
10.06
9 - 13.8 4.47
13 - 5.8
6.06
14
4.27
9 - 2.4
4.15
12 - 10.4
5.74
34
10.36
9 - 14.4 4.49
13 - 6.4
6.08
15
4.57
9 - 3.0
4.17
12 - 11.0
5.75
35
10.67
9 - 15.0 4.51
13 - 7.0
6.10
16
4.88
9 - 3.6
4.18
12 - 11.6
5.77
36
10.97
9 - 15.6 4.52
13 - 7.6
6.11
17
5.18
9 - 4.2
4.20
12 - 12.2
5.79
37
11.28
10 - 0.2 4.54
13 - 8.2
6.13
18
5.49
9 - 4.8
4.22
12 - 12.8
5.81
38
11.58
10 - 0.8 4.56
13 - 8.8
6.15
19
5.79
9 - 5.4
4.24
12 - 13.4
5.82
39
11.89
10 - 1.4 4.58
13 - 9.4
6.16
20
6.10
9 - 6.0
4.25
12 - 14.0
5.84
40
12.19
10 - 2.0 4.59
13 - 10.0
6.18
21
6.40
9 - 6.6
4.27
12 - 14.6
5.86
41
12.50
10 - 2.6 4.61
13 - 10.6
6.20
22
6.71
9 - 7.2
4.29
12 - 15.2
5.87
42
12.80
10 - 3.2 4.63
13 - 11.2
6.21
23
7.01
9 - 7.8
4.30
12 - 15.8
5.89
43
13.11
10 - 3.8 4.64
13 - 11.8
6.23
24
7.32
9 - 8.4
4.32
13 - 0.4
5.91
44
13.41
10 - 4.4 4.66
13 - 12.4
6.25
25
7.62
9 - 9.0
4.34
13 - 1.0
5.92
45
13.72
10 - 5.0 4.68
13 - 13.0
6.27
26
7.92
9 - 9.6
4.35
13 - 1.6
5.94
46
14.02
10 - 5.6 4.69
13 - 13.6
6.28
27
8.23
9 - 10.2 4.37
13 - 2.2
5.96
47
14.33
10 - 6.2 4.71
13 - 14.2
6.30
28
8.53
9 - 10.8 4.39
13 - 2.8
5.98
48
14.63
10 - 6.8 4.73
13 - 14.8
6.32
29
8.84
9 - 11.4 4.41
13 - 3.4
5.99
49
14.94
10 - 7.4 4.75
13 - 15.4
6.33
30
9.14
9 - 12.0 4.42
13 - 4.0
6.01
50
15.24
10 - 8.0 4.76
14
6.35
Table 1:
Hallowell Acadia Line Set Charging Chart
To prevent compressor damage or personal injury, observe the following:
Do not overcharge the system; follow the charging chart, weighing in New R-410A refrigerant; see
(Table 1 and 14, Appendix C)
.
Do not operate the Acadia outdoor unit in a vacuum or at negative pressure. Compressor failure would be imminent.
Содержание Acadia i Series
Страница 44: ...APPENDIX B WIRING DIAGRAMS 43 Figure 8 Line Voltage Wiring...
Страница 45: ...APPENDIX B WIRING DIAGRAMS 44 Figure 9 Hallowell Controller Wiring...
Страница 47: ...APPENDIX B WIRING DIAGRAMS 46 Figure 12 Entire Low Voltage Wiring with Electric Back Up...
Страница 48: ...APPENDIX B WIRING DIAGRAMS 47 Figure 13 Entire Low Voltage Wiring with Dual Fuel Back Up...
Страница 54: ...APPENDIX D ACADIA OUTDOOR UNIT MOUNTING 53 Figure 15 Typical Acadia Mounting...
Страница 56: ...APPENDIX E ACADIA COMPONENTS 55 Figure 17 Acadia Components...
Страница 57: ...APPENDIX F EWC ZONE CONTROL 56 Figure 18 Acadia with EWC Zone Control Wiring...