APPENDIX B – WIRING DIAGRAMS
48
Figure 14 – Compressor Starting Components
Acadia Starting Components
Acadia024
T81J195CBC
Primary
POE
Oil
GE Relay #
Coil
(kΩ)
PTCR #
(w/a)
Electrica
Relay #
Coil
(kΩ)
Start
Capacitor
Run
Capacitor
LRA RLA
Primary
Motor
Booster
Motor
1 Cylinder
37 oz
3ARR22J3U3 5.8 kΩ N/A RVAH2A13L 4.9 kΩ 216-259 mfd
@330 VAC
(1)
30 mfd @
440 VAC
30 5.1
(C-S)
2.74 Ω
(C-S)
2.11 Ω
2 Cylinders
3ARR22J24E3
7.0 kΩ
N/A
RVA4AQ3L 9.1 kΩ
65 8.8
(C-R)
0.80 Ω
(C-R)
0.85 Ω
H21J253ABC
Booster
42 oz 3ARR22J3S3
5.6 kΩ
305C20 RVA2AG3L 4.8 kΩ
145-175 mfd
@330 VAC
30 mfd @
370 VAC
61 10.7
(S-R)
3.54 Ω
(S-R)
2.96 Ω
Acadia036
T81J285CBC
Primary
POE
Oil
GE Relay #
Coil
(Ω)
PTCR #
(w/a)
Electrica
Relay #
Coil
(Ω)
Start
Capacitor
Run
Capacitor
LRA RLA
Primary
Motor
Booster
Motor
1 Cylinder
37 oz
3ARR22J8R3
(2)
5.6 kΩ
N/A
RVA9AG3L 3.6 kΩ
238-262 mfd
@330 VAC
40 mfd @
440 VAC
39 6.7
(C-S)
1.98 Ω
(C-S)
1.68 Ω
2 Cylinders
3ARR22J10C3
(3)
7.0 kΩ
N/A RVAH3A03L 7.0 kΩ
72 12
(C-R)
0.74 Ω
(C-R)
0.63 Ω
H21J343ABC
Booster
42 oz 3ARR22J3S3
5.6 kΩ
305C20 RVA2AG3L 4.8 kΩ
189-227 mfd
@330 VAC
45 mfd @
370 VAC
78 13.2
(S-R)
2.72 Ω
(S-R)
2.31 Ω
Acadia048
T81J384CBC
Primary
POE
Oil
GE Relay #
Coil
(Ω)
PTCR #
(w/a)
Electrica
Relay #
Coil
(Ω)
Start
Capacitor
Run
Capacitor
LRA RLA
Primary
Motor
Booster
Motor
1 Cylinder
37 oz
3ARR22J3L3
5.5 kΩ
N/A RVAH2AB3L 4.9 kΩ
324-356 mfd
@330 VAC
55 mfd @
440 VAC
45 7.5
(C-S)
1.55 Ω
(C-S)
1.40 Ω
2 Cylinders
3ARR22J4B3
14.5
kΩ
N/A RVAH6AN3L
11.8
kΩ
105 17.7
(C-R)
0.48 Ω
(C-R)
0.45 Ω
H20J443ABC
Booster
37 oz 3ARR22J3S3
5.5 kΩ
305C19 RVA2AG3L 4.8 kΩ
216-259 mfd
@330 VAC
(4)
65 mfd @
370 VAC
102 17.8
(S-R)
2.03 Ω
(S-R)
1.85 Ω
(1)
The Start Capacitor on the T81J195CBC was updated per a change of Bristol specifications to the 243-292 mfd @ 330 VAC in January, 2010.
Systems prior to the specifaction change used a 216-259 mfd @ 330 VAC start capacitor and is still considered usable equipment.
(2)
The 1 cylinder Relay on the T81J285CBC was updated per a change of Bristol specifactions to the 3ARR3J8R3 in January, 2010. The 3ARR22J8R3
has the same Pick-up and Drop-out voltages of the 3ARR3J8R3, but uses 50-amp rated contacts instead. Either relay is acceptable for use. Systems
prior to the specifaction change used the 3ARR22J3S3 and is still considered usable equipment.
(3)
The 2 cylinder Relay on the T81J285CBC was updated per a change of Bristol specifactions to the 3ARR22J10C3 in January, 2010. Systems prior
to the specifaction change used the 3ARRJ24C3 relay and is still considered usable equipment.
(4)
The Start Capacitor on the H20J443ABC was updated per a change of Bristol specifications to the 216-259 mfd @ 330 VAC in April, 2009.
Systems prior to the specification change used a 189-227 mfd @ 330 VAC and is still considered usable equipment.
Содержание Acadia i Series
Страница 44: ...APPENDIX B WIRING DIAGRAMS 43 Figure 8 Line Voltage Wiring...
Страница 45: ...APPENDIX B WIRING DIAGRAMS 44 Figure 9 Hallowell Controller Wiring...
Страница 47: ...APPENDIX B WIRING DIAGRAMS 46 Figure 12 Entire Low Voltage Wiring with Electric Back Up...
Страница 48: ...APPENDIX B WIRING DIAGRAMS 47 Figure 13 Entire Low Voltage Wiring with Dual Fuel Back Up...
Страница 54: ...APPENDIX D ACADIA OUTDOOR UNIT MOUNTING 53 Figure 15 Typical Acadia Mounting...
Страница 56: ...APPENDIX E ACADIA COMPONENTS 55 Figure 17 Acadia Components...
Страница 57: ...APPENDIX F EWC ZONE CONTROL 56 Figure 18 Acadia with EWC Zone Control Wiring...