FoamLogix, Model 2.1A and 1.7AHP Class
“A”
Electronic Foam Proportioning Systems
53
USER CALIBRATION
The complete Hale FoamLogix Systems; foam pump
and motor assembly, control unit and flow sensor, is
tested at the factory before shipping to the installer.
If the Hale FoamLogix system is properly installed,
further calibration IS NOT necessary until delivery to
customer.
The system permits easy checking of component
calibration to assure accurate operation. The
calibration process verifies component calibration
and allows adjustments to the flow sensor and
feedback sensor display readings, to allow for
variations in apparatus piping configurations and
end user selected foam concentrate.
Default values for simulated flow and foam
concentrate injection rate may be set to end user
specifications while in the calibration mode.
Note:
The Hale FoamLogix system is calibrated
at the factory to U.S. measurement (GPM, PSI,
GALLONS, etc.) units. The system may be set
to Metric units. (See heading
“English to Metric
Units” on page 58.) However, the same unit
of measurement must be used throughout the
calibration process to ensure proper proportioning
by the system.
Recalibration of the system may be required ONLY
after major repairs or component changes are made
to the Hale FoamLogix foam system. Different
viscosity foam concentrates may also required
recalibration.
ENTERING PASSWORDS
Entering passwords is accomplished using the
control unit function buttons.
To enter passwords, press and hold the
DISPLAY
button. The display shows
PASS,
then clears. While
continuing to hold the display button press the
or
buttons sequentially to enter the password. See
Table 25:
“Password Sequence.”
Table 25: Password Sequence
RESTORE FACTORY DEFAULTS
To return to the factory default values, enter the
restore factory values password (
) as
previously described.
Once the password is entered correctly the unit
displays
FAC
and returns to normal operation.
Factory default values:
Simulated Flow.... 150 GPM (568 LPM) %
FOAM .............. 0.5% Class
“A”
Also see Figure 26:
“Display - Password and
Calibration
Modes” on page 54.
CALIBRATION
1
To enter calibration password press and hold
the SELECT DISPLAY button (
i
). The display
shows PASS, then clears.
2
While holding
i
pressed, enter the calibration
password (
).
3
The display shows
CALL
for several seconds,
followed by
L (or O
when display is set to
metric). (See Figure 26:
“Display - Password
and Calibration
Modes” on page 54.)
The
FLOW
LED (Water Flow sensor
Calibration) also illuminates. (See Figure
27:
“Display - Flow Sensor Calibration” on
page 54.)
Mode
Password Sequence
User Calibration
Restore Factory Defaults
Содержание FoamLogix 1.7AHP
Страница 4: ...FoamLogix Model 2 1A and 1 7AHP Class A Electronic Foam Proportioning Systems 4 NOTES...
Страница 10: ...FoamLogix Model 2 1A and 1 7AHP Class A Electronic Foam Proportioning Systems 10...
Страница 14: ...FoamLogix Model 2 1A and 1 7AHP Class A Electronic Foam Proportioning Systems 14 NOTES...
Страница 25: ...FoamLogix Model 2 1A and 1 7AHP Class A Electronic Foam Proportioning Systems 25 p n 038 1570 08 0...
Страница 28: ...FoamLogix Model 2 1A and 1 7AHP Class A Electronic Foam Proportioning Systems 28 NOTES...
Страница 47: ...FoamLogix Model 2 1A and 1 7AHP Class A Electronic Foam Proportioning Systems 47 Figure 22 Extra Cable Storage...
Страница 52: ...FoamLogix Model 2 1A and 1 7AHP Class A Electronic Foam Proportioning Systems 52 NOTES...
Страница 68: ...FoamLogix Model 2 1A and 1 7AHP Class A Electronic Foam Proportioning Systems 68 NOTES...
Страница 79: ...NOTES FoamLogix Model 2 1A and 1 7AHP Class A Electronic Foam Proportioning Systems 77...