Seivice diagnosis
Domestic air conditioner
Check whether Terminal on the outdoor
mainboard is well inserted.
Is it normal?
Yes
NO
Reinsert the terminals
Electrify the machine again and turn it
on in the Cool state with the remote
controller. check whether motor can
run
˛
Yes
Measure the voltage between 3 and 6 of
the terminal about 0-5v.
Is it normal?
N0
The motor of the outdoor unit is damaged
and needs replacing.
Measure the voltage between 1 and 3 of the terminal of
fan motor on the mainboard about DC310V, Measure
the voltage between 3 and 4 of the terminal about
DC15V. Measure the voltage between 5 and 3 of the
terminal about 1-6v.
NO
Is it normal?
The mainboard of the outdoor unit is
damaged and needs replacing
N0
Yes
Yes
35
Содержание N-Series
Страница 47: ...Circuit diagrams Domestic air conditioner 12 Circuit diagrams 45 ...
Страница 48: ...Circuit diagrams Domestic air conditioner 46 ...
Страница 51: ...Removal of procedure 1 Removal of Air Filter 1 Domestic Air Condition ...
Страница 54: ...Removal of procedure three two HOOKS 4 Domestic Air Condition ...
Страница 55: ...Removal of procedure 3 Removal of horizontal flap flap flap flap flap 5 Domestic Air Condition ...
Страница 56: ...Removal of procedure 4 Removal of Drain pan 6 Domestic Air Condition ...
Страница 57: ...Removal of procedure 5 Removal of vertical blades and swing motor 7 Domestic Air Condition ...
Страница 58: ...Removal of procedure 6 Removal of Electrical Box 8 Domestic Air Condition ...
Страница 59: ...Removal of procedure 7 Removal of Heat Exchanger 9 Domestic Air Condition ...
Страница 60: ...Removal of procedure 10 Domestic Air Condition ...
Страница 61: ...Removal of procedure 8 Removal of Fan Rotor and Motor 11 Domestic Air Condition ...
Страница 62: ...Removal of procedure 12 Domestic Air Condition ...