Install air ducting
There are no obstacles in the 2000mm above the outdoor unit; When there are obstacles in the outer plane,
there must be a pilot channel, and the wind will be free, the wind will not beshort-circuited, and the external static
pressure will be less than 110Pa. Airway design dimensions are as follows:
Channel size (pattern 1)
Channel size (pattern 2)
AV08~14IMVURA
AV16~22IMVURA
A The inner diameter 980 The inner diameter 1410
B
The inner diameter750 The inner diameter 750
C
≤10000
≤10000
D
E+750
E+750
E
≥300
≥300
F
≥320
≥320
AV08~14IMVURA
AV16~22IMVURA
A The inner diameter 750 The inner diameter 750
B The inner diameter 980 The inner diameter 1410
C
≤10000
≤10000
D
E+980
E+1410
E
≥300
≥300
F
≥320
≥320
A
C
D
E
F
B
A
C
D
E
F
B
Note:
Before installing the wind channel, the unit should be removed from the wind protection network. At the same time,
the outdoor air tube static press is set up to "have static pressure" mode. The above is just an example, the length
of the wind tunnel should be calculated according to the shape of the wind channel.
Содержание MRV 5-RC VP1-112B
Страница 1: ...MRV 5 RC Service Manual SYJS 03 2019REV A Edition 2019 03 ...
Страница 3: ......
Страница 55: ...52 AV08 10 12 14IMVURA 4 Center of gravity x X 347 9587 y 471 5454 z 725 6683 y z ...
Страница 56: ...53 AV16 18 20 22IMVURA x X 650 5962 y 380 7255 z 706 5342 y z ...
Страница 106: ...103 2 Dimension 4 19 200 60 25 25 25 249 108 232 84 69 388 73 82 65 103 177 4 44 4 35 277 ...
Страница 116: ...113 2 Preparation before installation ...
Страница 130: ...127 2 Dimension 290 67 410 220 567 137 160 189 57 144 109 159 159 212 393 4 22 65 65 65 65 65 44 65 76 4 52 67 156 830 ...
Страница 162: ...159 One by one valve box PCB code 0151800186A 2 Valve box PCB photo and dip switch setting ...
Страница 165: ...162 One by four valve box PCB code 0151800466 ...