In installation, please check specially the below items:
•
If the connected units quantity and the total capacity is in the allowable range?
•
If the refrigerant pipe length is in the limited range?
• If the pipe size is proper? And if the pipe is installed horizontally?
• If the branch pipe is installed horinzontally or vertically?
•
If the additional refrigerant is counted correctly and weighed by the standard balance?
•
If there is refrigerant leakage?
•
If all the indoor power supplies can be on/off simultaneously?
•
If the power voltage is in compliance with the data marked on the rating label?
•
If the address of indoors and outdoors has been set?
Before installation
10.2. Installation instruction
1) Before installation, check if the model, power supply, pipe, wires and parts purchased respectively are correct.
2) Check if the indoors and outdoors can be combined as the following.
Outdoor
Indoor
HP
Capacity (100W)
Combination type
Indoor Qty
Total indoor capacity (HP)
Gather
pipe
8
224
Single (8HP)
1~15
4~10.4
-
10
280
Single (10HP)
1~17
5~13
-
12
335
Single (12HP)
1~20
6~15.6
-
14
400
Single (14HP)
1~24
7~18.2
-
16
450
Single (16HP)
1~27
8~20.8
-
18
504
Single (18HP)
1~30
9~23.4
-
20
560
Single (20HP)
1~33
10~26
-
22
615
Single (22HP)
1~36
11~28.6
-
24
680
Combination (335+335)
1~40
12~31.2
HZG-R20B
26
735
Combination (335+400)
1~43
13~33.8
28
800
Combination (400+400)
1~46
14~36.4
30
850
Combination (400+450)
1~50
15~39
32
900
Combination (450+450)
1~53
16~41.6
34
954
Combination (450+504)
1~57
17~44.2
36
1008
Combination (504+504)
1~60
18~46.8
38
1064
Combination (504+560)
1~64
19~49.4
40
1120
Combination (560+560)
1~64
20~52
42
1175
Combination (560+615)
1~64
21~54.6
44
1230
Combination (615+615)
1~64
22~57.2
46
1300
Combination (400+450+450)
1~64
23~59.8
HZG-R30B
48
1350
Combination (450+450+450)
1~64
24~62.4
50
1404
Combination (450+450+504)
1~64
25~65
52
1458
Combination (450+504+504)
1~64
26~67.6
54
1512
Combination (504+504+504)
1~64
27~70.2
56
1568
Combination (504+504+560)
1~64
28~72.8
58
1624
Combination (504+560+560)
1~64
29~75.4
60
1680
Combination (560+560+560)
1~64
30~78
62
1735
Combination (560+560+615)
1~64
31~80.6
64
1790
Combination (560+615+615)
1~64
32~83.2
66
1845
Combination (615+615+615)
1~64
33~85.8
Содержание MRV 5-RC VP1-112B
Страница 1: ...MRV 5 RC Service Manual SYJS 03 2019REV A Edition 2019 03 ...
Страница 3: ......
Страница 55: ...52 AV08 10 12 14IMVURA 4 Center of gravity x X 347 9587 y 471 5454 z 725 6683 y z ...
Страница 56: ...53 AV16 18 20 22IMVURA x X 650 5962 y 380 7255 z 706 5342 y z ...
Страница 106: ...103 2 Dimension 4 19 200 60 25 25 25 249 108 232 84 69 388 73 82 65 103 177 4 44 4 35 277 ...
Страница 116: ...113 2 Preparation before installation ...
Страница 130: ...127 2 Dimension 290 67 410 220 567 137 160 189 57 144 109 159 159 212 393 4 22 65 65 65 65 65 44 65 76 4 52 67 156 830 ...
Страница 162: ...159 One by one valve box PCB code 0151800186A 2 Valve box PCB photo and dip switch setting ...
Страница 165: ...162 One by four valve box PCB code 0151800466 ...