Combinations
• This series is cooling and heating heat recovery models. Only when the system is equipped with valve box, indoor
units under different valve boxes can achieve cooling and heating simultaneously. The modes of the indoors
which under the same valve box should be the same. If the indoors connected without valve box, the indoors
only can do cooling mode.
Do not connect the valve box to the common multi-split system, as the former is
dedicated to the cooling & heating multi-split system.
• Concerning the model of the connectible indoor unit, see the sample brochure, etc. for confirmation.
•
Concerning the total capacity of the indoor unit connected at the downstream of the valve box (the total selected
capacity of the models), select in Table 1 according to the quantity (refer to Table 2 for the selected capacity of
the model of each indoor unit)
Table1: Total capacity of indoor unit:
Table 2: Capacity measure and selected capacity of the model of indoor unit
Valve box
Total capacity of indoor unit (kW)
Quantity of indoor unit
112B
Less than 11.2
Less than 5
180B
11.2~18.0
Less than 8
280B
18.0~28.0
Less than 8
Capacity measure
072 092 122 162 182 242 282 302 382 482 722 962
selected capacity (kW)
2.2 2.8 3.6 4.5 5.6 7.0 8.0 9.0 11.2 14.0 22.6 28
Do not connect the fresh air unit (AD*MPERA, YV4VXH*WAR--GX) to this system.
<Selected example> one AD072MLERA, YVDVXH022WAR--GX,
two AD182MLERA,YVDVXH056WAR--GX, upon connection:
Total capacity of indoor units =2.2 kW+5.6 kW×2=13.4 kW
Select 180B
(2) Inspection upon delivery
Inspection item
Inspection column
If the electric box cover is installed
If the installation specification is transferred to the customer
Inspection item
Pay much attention to the following during installation. Check them again after completion.
(1) Inspection items after installation
Inspection item
Defect
Inspection
column
If the installation of valve box is secure ?
Falling off, vibration and noise
If gas leakage inspection is completed ?
No heating/cooling
If complete insulation is achieved (refrigerant piping and tubing
connections) ?
Water leakage
If the voltage of the power supply is consistent with that on the
nameplate ?
Out of service, burnt
If there is improper wiring or piping ?
Out of service, burnt
If there is construction without grounding ?
If the thickness of the wire is as specified ?
Out of service, burnt
Содержание MRV 5-RC VP1-112B
Страница 1: ...MRV 5 RC Service Manual SYJS 03 2019REV A Edition 2019 03 ...
Страница 3: ......
Страница 55: ...52 AV08 10 12 14IMVURA 4 Center of gravity x X 347 9587 y 471 5454 z 725 6683 y z ...
Страница 56: ...53 AV16 18 20 22IMVURA x X 650 5962 y 380 7255 z 706 5342 y z ...
Страница 106: ...103 2 Dimension 4 19 200 60 25 25 25 249 108 232 84 69 388 73 82 65 103 177 4 44 4 35 277 ...
Страница 116: ...113 2 Preparation before installation ...
Страница 130: ...127 2 Dimension 290 67 410 220 567 137 160 189 57 144 109 159 159 212 393 4 22 65 65 65 65 65 44 65 76 4 52 67 156 830 ...
Страница 162: ...159 One by one valve box PCB code 0151800186A 2 Valve box PCB photo and dip switch setting ...
Страница 165: ...162 One by four valve box PCB code 0151800466 ...