35
Model
AV60IMVURA
AV62IMVURA
Outdoor
fan
Brand
Tian Da+Tian Da+Tian Da
Tian Da+Tian Da+Tian Da
Model
/
/
Material
ABS+20%GF
ABS+20%GF
Type
Axial
Axial
Diameter
mm
Φ642+Φ642+Φ642
Φ642+Φ642+Φ642
Height
mm
198+198+198
198+198+198
Outdoor
coil
Number of rows
3+3+3
3+3+3
Tube pitch(a)x row pitch(b)
mm
21×18.186
21×18.186
Fin spacing
mm
1.60
1.60
Fin type (code)
Hydrophilic aluminum
Hydrophilic aluminum
Fin Coating Type
Optional
Clear lacquer
Clear lacquer
Salt Spray Test Duration
Hour
168
168
Tube outside dia.and type
INNERGROOVE TUBE
INNERGROOVE TUBE
mm
Ф7
Ф7
Coil length x height
mm
(2843*1260+2757*1260+2669*1260)+(2843*1260+2757*1260
+2669*1260)+(2843*1260+2757*1260+2669*1260)
Number of circuits
30+30+30
30+30+30
Cabinet
coating
Coating type
Powder Coating
Powder Coating
Salt Spray Test Duration
Hour
72
72
Sheet Metal Material
Hot zinc plate
Hot zinc plate
Sheet Metal Thickness
mm
1
1
Control panel enclosure IP class
standard
IP24
IP24
Outdoor air flow (cooling / heating)
m3/h
57000
57000
External static pressure
Pa
110
110
Outdoor sound level(sound pressure level )(H)
dB(A)
68
68
Outdoor sound level(sound power level ) (H)
dB(A)
89
89
Outdoor
unit
Dimension(W*D*H)
mm
1410/750/1690+1410/750/1690+1410/750/1690
Packing (W*D*H)
mm
1515/850/1838+1515/850/1838+1515/850/1838
Net weight
kg
1125
1125
Gross weight
kg
1212
1212
Refrigerant
Type
R410A
R410A
Charged volume
kg
10
10
Throttle type
EXV
EXV
Design pressure
MPa
4.15
4.15
Refrigerant
piping
Liquid pipe
mm
19.05
19.05
Gas pipe
mm
41.3
41.3
High gas pipe
mm
38.1
38.1
Oil pipe
mm
/
/
Total pipe length
m
1000
1000
Max. pipe length(Equivalent/ Actual)
m
260/220
260/220
Max. Diff. indoor/outdoor unit*1
m
110/90
110/90
Standard Diff. indoor/outdoor unit
m
50/40
50/40
Max. / standard Diff. indoor/indoor unit*1
m
30/18
30/18
Connectable indoor unit ratio
%
50~130
50~130
Maximum indoor units
Piece
64
64
Connection
wiring
Max. fuse current
A
189
189
Min. wiring current
A
158.54
160.20
Power wiring
mm2
70.00
70.00
Signal wiring
mm2
2
X 0.75
2
X 0.75
Operation Range
°C
Cooling: -5~50 Heating: -23~21 Cooling: -5~50 Heating: -23~21
Norminal condition: indoor temperature (cooling): 27°C DB/19°C WB, indoor temperature (heating): 20°C DB/14.5°C WB.
Outdoor temperature(cooling): 35°C DB/24°C WB, outdoor temperature(heating): 7°C DB/6°C WB The data is measured with 7.5m equivalent
pipe and 0 m height difference.
The noise level will be measured in the third octave band limited values in the semi-anechoic chamber, using a Real Time Analyser calibrated
sound intensity meter. It is a sound pressure noise level.
*1 If the total pipe length is from 500 to 1000m or the height difference between the outdoor and indoor units is from 50 to 110m or the height
difference between the indoor units is from 18 to 30m, you Must contact your local distributor/dealer for individual design and production.
Содержание MRV 5-RC VP1-112B
Страница 1: ...MRV 5 RC Service Manual SYJS 03 2019REV A Edition 2019 03 ...
Страница 3: ......
Страница 55: ...52 AV08 10 12 14IMVURA 4 Center of gravity x X 347 9587 y 471 5454 z 725 6683 y z ...
Страница 56: ...53 AV16 18 20 22IMVURA x X 650 5962 y 380 7255 z 706 5342 y z ...
Страница 106: ...103 2 Dimension 4 19 200 60 25 25 25 249 108 232 84 69 388 73 82 65 103 177 4 44 4 35 277 ...
Страница 116: ...113 2 Preparation before installation ...
Страница 130: ...127 2 Dimension 290 67 410 220 567 137 160 189 57 144 109 159 159 212 393 4 22 65 65 65 65 65 44 65 76 4 52 67 156 830 ...
Страница 162: ...159 One by one valve box PCB code 0151800186A 2 Valve box PCB photo and dip switch setting ...
Страница 165: ...162 One by four valve box PCB code 0151800466 ...