84
C. Pipe spec and the torque
Diameter (mm)
Torque(N.m)
Ø6.35
16~20
Ø9.52
40~50
Ø12.7
40~50
Ø15.88
90~120
Ø19.05
100~140
Not less than Ø22.22
No requirement,
due to braze connector
Branch pipe
Branch pipe selection:
Total indoor capacity (100W)
Model(optional)
3 pipes
2 Pipes
X < 335
FQG-R335A
FQG-B335A
335 ≤ X < 506
FQG-R506A
FQG-B506A
506 ≤ X < 730
FQG-R730A
FQG-B730A
730 ≤ X < 1350
FQG-R1350A
FQG-B1350A
X ≥ 1350
FQG-R2040A
FQG-B2040A
Outdoor unit type
The master unit will choose the closest one to the 1st branch pipe.
Note:
1. When connecting the gather pipe and the outdoor, please pay attention to the outdoor pipe dimension.
2. When adjusting the diameter among gather pipes and among the units, please must execute at the branch pipe
side.
3. Please install the gather pipe(gas/liqiud side) in horizontal or vertical direction.
4. When welding with hard solder, please must blow nitrogen. If not, a number of oxide will be produced and cause
heavy damage.Besides,to prevent water and dust into the pipe, please make the brim as outer roll.
Adhesive side
Prepare on field
Seal the connection and wrap the
heat insulator with adhesive tape
Cut off pipe with the cutter
Floor
Floor
Right
Horizontal
Cut off at the middle
Wrong
B. Indoor unit
Model
Gas pipe side
Liquid pipe side
Diameter
(mm)
Connecting
method
Diameter
(mm)
Connecting
method
07
Ø9.52
Flared
Ø6.35
Flared
09
Ø9.52
Ø6.35
12
Ø12.7
Ø6.35
16
Ø12.7
Ø6.35
18
Ø12.7
Ø6.35
24
Ø15.88
Ø9.52
28
Ø15.88
Ø9.52
30
Ø15.88
Ø9.52
38
Ø15.88
Ø9.52
48
Ø15.88
Ø9.52
Note:
AS072 AS092 gas pipe / liquid pipe: Ø12.7mm/6.35mm;
AS182 gas pipe / liquid pipe: Ø15.88/9.52mm
Содержание MRV 5-RC VP1-112B
Страница 1: ...MRV 5 RC Service Manual SYJS 03 2019REV A Edition 2019 03 ...
Страница 3: ......
Страница 55: ...52 AV08 10 12 14IMVURA 4 Center of gravity x X 347 9587 y 471 5454 z 725 6683 y z ...
Страница 56: ...53 AV16 18 20 22IMVURA x X 650 5962 y 380 7255 z 706 5342 y z ...
Страница 106: ...103 2 Dimension 4 19 200 60 25 25 25 249 108 232 84 69 388 73 82 65 103 177 4 44 4 35 277 ...
Страница 116: ...113 2 Preparation before installation ...
Страница 130: ...127 2 Dimension 290 67 410 220 567 137 160 189 57 144 109 159 159 212 393 4 22 65 65 65 65 65 44 65 76 4 52 67 156 830 ...
Страница 162: ...159 One by one valve box PCB code 0151800186A 2 Valve box PCB photo and dip switch setting ...
Страница 165: ...162 One by four valve box PCB code 0151800466 ...