1. If the supply cord is damaged, it must be replaced by the manufacturer or its
service agent or a similar quali
¿
ed person. The type of connecting wire is
H05RN-F or H07RN-F.
2. If the fuse on PC board is broken please change it with the type of
T. 3.15A/250V.
3. The wiring method should be in line with the local wiring standard.
4. After installation, the power plug should be easily reached.
5. A breaker should be incorporated into
¿
xed wiring. The breaker should be
all-pole switch and the distance between its two contacts should be not less
than 3mm.
Outdoor unit
Install according to
Drawing for the installation of indoor and outdoor units
To bend a pipe, give the roundness as large as possible not to crush the pipe ,
ƽ
and the bending radius should be 30 to 40 mm or longer.
Connecting the pipe of gas side
¿
rst makes working easier.
ƽ
The connection pipe is specialized for R410A.
ƽ
Installation of Outdoor Unit
Half union
Flare nut
Torque wrench
Be careful that matters, such as wastes of sands, etc. shall not enter the pipe.
The standard pipe length is 5m. If it is over 7m, the function of the unit will be
affected. If the pipe has to be lengthened, the refrigerant should be charged,
according to 20 g/m. But the charge of refrigerant must be conducted by profes-
sional air conditioner engineer. Before adding additional refrigerant, perform air
purging from the refrigerant pipes and indoor unit using a vacuum pump,then
Spanner
Forced fastening without careful centering may
damage the threads and cause a leakage of gas.
Pipe Diameter(
Ǜ
)
Fastening torque
Liquid side6.35mm(1/4")
18N.m
Liquid/Gas side9.52mm(3/8")
42 N.m
Gas side 12.7mm(1/2")
55N.m
Gas side 15.88mm(5/8")
60 N.m
Connection of pipes
charge additional refrigerant.
Outdoor unit
Indoor unit
A
B
Outdoor unit
Indoor unit
A
B
A
B
Outdoor unit
Indoor unit
Oil trap
CAUTION
Max.Elevation: Amax=15m
Ɣ
In case the elevation A is more
Ɣ
than 5m, oil trap shoud be
installed every 5~7m
Max. Length: Bmax=25m
Ɣ
In case the pipe length B is
Ɣ
more than 10m, the refrigerant
should be charged, according
to 20 g/m.
Use the same method on indoor unit. Loosen the screws on
ƽ
terminal block and
insert the plugs fully into terminal block, then tighten the screws.
Insert the cable according to terminal number in the same manner as the indoor
unit.
ƽ
If wiring is not correct, proper operation can not be carried out and controller
may be damaged.
ƽ
Fix the cable with a clamp.
ƽ
Connection
If the drain-elbow is used,
ƽ
please attach it as
¿
gure. (Note:
Only for heat pump unit.)
Detach the service port’s cap of
1.
3-way valve, the valve rod’s cap for 2-way valve
and 3-way’s, connect the service port into the projection of charge hose (Iow)
for gaugemanifold. Then connect the projection of charge hose (center) for gau-
gemanifold into vacuum pump.
Open the handle at Iow in
2.
gaugemanifold, operate vacuum pump. If the scale-
moves of gause (Iow) reach vacuum condition in a moment, check 1. again.
Vacuumize for over 15min.And check the level gauge which should read -0.1MPa
3.
(76 cm Hg) at Iow pressure side. After the completion of vacuumizing, close the
handle ‘Lo’ in gaugemanifold and stop the operation of the vacuum pump. Check
condition of the scale and hold it for 1-2min. If the scale-moves back in spite of
tightening, make
À
aring work again, the return to the beginning of 3 .
Attaching Drain-Elbow
Purging Method:To use vacuum pump
Open the valve rod for the 2-way valve to an angle of
4.
anticlockwise 90 degrees.
After 6 seconds, close the 2-way valve and make the inspection of gas leakage.
Outdoor unit A
4G0.75mm
2
3
2
^
POWER
1
)
(N
)
(L
)
(C
3
2
1
)
(N
)
(L
)
(C
Power cable:
HSU18VHJ(DB)
3G2.5mm
2
HSU12VHJ(DB)
2
4G0.75mm
Outdoor unit
3
2
^
POWER
1
)
(N
)
(L
)
(C
3
2
1
)
(N
)
(L
)
(C
Indoor unit
Indoor unit
Power cable:
3G1.5mm
2
+68
12/
VHJ(DB)
Installations
70
Содержание HSU18VHJ(DB)
Страница 3: ...12 VHJ DB 101 101 102 106 ...
Страница 13: ...Domestic Air Conditioner PCB 1 CN31 CN11 CN1 CN32 CN26 CN27 CON2 CN30 CON12 CON8 CH1 10 HSU12 18VHJ DB ...
Страница 15: ... Domestic Air Conditioner PCB 1 CN26 CON1 CON2 CN11 CN32 CN1 CN48 CON8 CON6 CON7 12 HSU12 18VHJ DB ...
Страница 18: ...Domestic Air Conditioner PCB 2 CN1 CN2 CN3 CN4 CN5 CN6 CN7 CN11 CN10 15 HSU12 18VHJ DB ...
Страница 21: ... Domestic Air Conditioner PCB 2 CN1 CN2 CN3 CN4 CN5 CN6 CN7 CN11 CN10 18 HSU12 18VHJ DB ...
Страница 94: ...9 3 1 Removal of Outdoor Panel 9 3 For 12 18K Outdoor unit Removal Procedure HSU12 18VHJ DB 91 ...
Страница 95: ...Loosen the top panel screws 1 2 Lift the top panel HSU12 18VHJ DB Removal Procedure 92 ...
Страница 96: ...Domestic air conditioner Removal Procedure Loosen the csrews and pull the panel HSU12 18VHJ DB 93 ...
Страница 97: ...9 3 2 Removal of Electrical Box HSU12 18VHJ DB Removal Procedure 94 ...
Страница 98: ...9 3 3 Removal of Fan and Fan Motor HSU12 18VHJ DB Removal Procedure 95 ...
Страница 99: ...2 Loosen the fixing screws and remove the motor HSU12 18VHJ DB Removal Procedure 96 ...
Страница 100: ...9 3 4 Removal of fan motor Bracket and Partition HSU12 18VHJ DB Removal Procedure 97 ...
Страница 101: ...and remove the reactor Loosen the screw HSU12 18VHJ DB Removal Procedure 98 ...
Страница 103: ...4 Remove the compre ssor and pipe assay 5 Remove the conden ser HSU12 18VHJ DB Removal Procedure 100 ...
Страница 104: ... SSHQGL SSHQGL 3LSLQJ LDJUDPV 68 9 101 ...
Страница 109: ...10 3 Circuit Diagrams 10 3 1 INDOORUNIT FOR12K Appendix HSU12 18VHJ DB 106 ...