Domestic Air Conditioner
TE
C×TA
ˉ
Į
Among which: C:TA
˘
0
ć
ˈ
C=0.8
TA
0
ć
ˈ
C=0.6
For area prone to frost, the value is set at 6 when unit leaves the factory.
Defrosting entry temperature control -15
C×TA
ć
ˉ
Į
-5
ć
Defrosting Time Interval
time interval between two defrosting cycles is 45 minutes.
Defrosting Operation
When defrosting begins, compressor will stop for one minute, external fan is running and 50s later,
four-way valve will be off.
When compressor starts, external fan will be off, compressor will run at 58Hz for 60s then move on to
target frequency of 88Hz.
During defrosting, compressor current and air discharge overheat protection features are effective.
During defrosting, if compressor shuts down due to activation of protection feature or due to
malfunction, it will resume after 3 minutes. In the unit is still within defrosting cycle, it will resume
defrosting and startup of compressor will be based on the rule for defrosting startup. (The unit will exit
defrosting mode and handle fault in the event of 3 consecutive restart failures.)
On entering defrosting, it must guarantee that compressor will operate for a minimum of 2 minutes in
defrosting mode before exit.
Defrosting Exit Condition
When one of the following conditions is met, defrosting operation will be switched to heating
operation.
˄
1
˅
:Temperature of outdoor heat exchanger exceeds 7
for 80s continuously
ć
˄
2
˅
: Temperature of outdoor heat exchanger exceeds 12
for 5s continuously
ć
˄
3
˅
:Defrosting operation continues for 11 minutes.
When defrosting exit conditions are met, the unit will operate as follows
Compressor stops and external fan starts, 50s later, four-way valve will be on, 60s later, compressor
will operate as per startup process.
5.2.5 PTC Output Control
When outdoor unit is energized, PTC output value is 0, 10s later, output value is 1.
When compressor stops for 10 minutes continuously, PTC output value is 0.
On receiving compressor startup instruction, initial PTC output is 1, and compressor startup will be
performed 5s later.
HSU12/18VHJ(DB)
2
7
Содержание HSU18VHJ(DB)
Страница 3: ...12 VHJ DB 101 101 102 106 ...
Страница 13: ...Domestic Air Conditioner PCB 1 CN31 CN11 CN1 CN32 CN26 CN27 CON2 CN30 CON12 CON8 CH1 10 HSU12 18VHJ DB ...
Страница 15: ... Domestic Air Conditioner PCB 1 CN26 CON1 CON2 CN11 CN32 CN1 CN48 CON8 CON6 CON7 12 HSU12 18VHJ DB ...
Страница 18: ...Domestic Air Conditioner PCB 2 CN1 CN2 CN3 CN4 CN5 CN6 CN7 CN11 CN10 15 HSU12 18VHJ DB ...
Страница 21: ... Domestic Air Conditioner PCB 2 CN1 CN2 CN3 CN4 CN5 CN6 CN7 CN11 CN10 18 HSU12 18VHJ DB ...
Страница 94: ...9 3 1 Removal of Outdoor Panel 9 3 For 12 18K Outdoor unit Removal Procedure HSU12 18VHJ DB 91 ...
Страница 95: ...Loosen the top panel screws 1 2 Lift the top panel HSU12 18VHJ DB Removal Procedure 92 ...
Страница 96: ...Domestic air conditioner Removal Procedure Loosen the csrews and pull the panel HSU12 18VHJ DB 93 ...
Страница 97: ...9 3 2 Removal of Electrical Box HSU12 18VHJ DB Removal Procedure 94 ...
Страница 98: ...9 3 3 Removal of Fan and Fan Motor HSU12 18VHJ DB Removal Procedure 95 ...
Страница 99: ...2 Loosen the fixing screws and remove the motor HSU12 18VHJ DB Removal Procedure 96 ...
Страница 100: ...9 3 4 Removal of fan motor Bracket and Partition HSU12 18VHJ DB Removal Procedure 97 ...
Страница 101: ...and remove the reactor Loosen the screw HSU12 18VHJ DB Removal Procedure 98 ...
Страница 103: ...4 Remove the compre ssor and pipe assay 5 Remove the conden ser HSU12 18VHJ DB Removal Procedure 100 ...
Страница 104: ... SSHQGL SSHQGL 3LSLQJ LDJUDPV 68 9 101 ...
Страница 109: ...10 3 Circuit Diagrams 10 3 1 INDOORUNIT FOR12K Appendix HSU12 18VHJ DB 106 ...