Domestic Air Conditioner
5.2.6.4 Outdoor Temperature Limit
Cooling: When outdoor temperature is lower than 23
, cooling operation will start, compressor
ć
frequency is limited to less than 50 HZ, outdoor wind speed is forced at level 1.
Heating: When outdoor temperature is higher than 18
, heating operation will start, compressor
ć
frequency is limited to less than 53 HZ, outdoor wind speed is forced at level 1.
5.2.6.5 Special Features
1. Forced Cooling: When receiving indoor forced cooling signal, cooling operation will start in a
frequency signaled by indoor unit. Only air discharge temperature and over current protection features
are effective and other protection features are invalid.
2. Rated, Middle and Minimum Capacity Operation: When receiving indoor, rated, middle and
minimum capacity operation signal, outdoor unit will operate as per wind speed and frequency set by
EEPROM and all the protection features are effective.
5.2.6.6 Fault Display and Treatment
In case outdoor unit faults, the alarm indicator lamp will blink and blink frequency is 1HZ
ˈ
Time interval
between blink cycles is 3s.
Alarm indicator lamp is off when there is no fault.
HSU12/18VHJ(DB)
2
9
Содержание HSU18VHJ(DB)
Страница 3: ...12 VHJ DB 101 101 102 106 ...
Страница 13: ...Domestic Air Conditioner PCB 1 CN31 CN11 CN1 CN32 CN26 CN27 CON2 CN30 CON12 CON8 CH1 10 HSU12 18VHJ DB ...
Страница 15: ... Domestic Air Conditioner PCB 1 CN26 CON1 CON2 CN11 CN32 CN1 CN48 CON8 CON6 CON7 12 HSU12 18VHJ DB ...
Страница 18: ...Domestic Air Conditioner PCB 2 CN1 CN2 CN3 CN4 CN5 CN6 CN7 CN11 CN10 15 HSU12 18VHJ DB ...
Страница 21: ... Domestic Air Conditioner PCB 2 CN1 CN2 CN3 CN4 CN5 CN6 CN7 CN11 CN10 18 HSU12 18VHJ DB ...
Страница 94: ...9 3 1 Removal of Outdoor Panel 9 3 For 12 18K Outdoor unit Removal Procedure HSU12 18VHJ DB 91 ...
Страница 95: ...Loosen the top panel screws 1 2 Lift the top panel HSU12 18VHJ DB Removal Procedure 92 ...
Страница 96: ...Domestic air conditioner Removal Procedure Loosen the csrews and pull the panel HSU12 18VHJ DB 93 ...
Страница 97: ...9 3 2 Removal of Electrical Box HSU12 18VHJ DB Removal Procedure 94 ...
Страница 98: ...9 3 3 Removal of Fan and Fan Motor HSU12 18VHJ DB Removal Procedure 95 ...
Страница 99: ...2 Loosen the fixing screws and remove the motor HSU12 18VHJ DB Removal Procedure 96 ...
Страница 100: ...9 3 4 Removal of fan motor Bracket and Partition HSU12 18VHJ DB Removal Procedure 97 ...
Страница 101: ...and remove the reactor Loosen the screw HSU12 18VHJ DB Removal Procedure 98 ...
Страница 103: ...4 Remove the compre ssor and pipe assay 5 Remove the conden ser HSU12 18VHJ DB Removal Procedure 100 ...
Страница 104: ... SSHQGL SSHQGL 3LSLQJ LDJUDPV 68 9 101 ...
Страница 109: ...10 3 Circuit Diagrams 10 3 1 INDOORUNIT FOR12K Appendix HSU12 18VHJ DB 106 ...