Domestic Air Conditioner
5.2.6 System Protection Function
5.2.6.1 3 minutes stand-by time
Time interval between compressor shutdown and restart is set at 3 minutes to ensure that compressor
will only restart after 3-minute shutdown and initial energization valves are turned on to adequate
opening position after being fully turned off.
5.2.6.2 TD High Temperature Protections
As long as unit is on, the TD air discharge overheat protection feature will be activated, yet air
discharge sensor fault must be alarmed 4 minutes after compressor starts.
TD
˄
ć
˅
Abnormal Shutdown
117
Rapid frequency drop
˄
1HZ/s
˅
112
Slow frequency drop (1HZ/10s)
108
Invariable frequency
105
Frequency rise (1HZ/10s)
98
Frequency rise
˄
1HZ/1 s
˅
When TD>117
for 20s continuously
ć
ˈ
air discharge overheat protection will be activated and fault will
be reported to indoor unit.
It will not continue in other conditions.
5.2.6.3 Indoor Heat Exchanger Anti-freeze Protection
Anti-freeze during cooling
9
ć
1Hz/10sec 6
ć
5
ć
0
ć
When TC < 5
ć
ˈ
compressor frequency will drop at a speed of 1HZ/10s
When TC starts to rise
ˈ
and 6
TC
9
ć
ˈ
compressor frequency will remain unchanged.
When 9 < TC < 11
, frequ
ć
ency will rise nomal.
If TC
0
ć
ˈ
for 2 consecutive minutes, compressor will shutdown and outdoor fault lamp blinks. Fault
will not be reported to indoor unit.
When compressor shuts down for more than3 minutes
ˈ
and when TC>9
ć
ˈ
compressor will restart.
HSU12/18VHJ(DB)
2
8
Содержание HSU18VHJ(DB)
Страница 3: ...12 VHJ DB 101 101 102 106 ...
Страница 13: ...Domestic Air Conditioner PCB 1 CN31 CN11 CN1 CN32 CN26 CN27 CON2 CN30 CON12 CON8 CH1 10 HSU12 18VHJ DB ...
Страница 15: ... Domestic Air Conditioner PCB 1 CN26 CON1 CON2 CN11 CN32 CN1 CN48 CON8 CON6 CON7 12 HSU12 18VHJ DB ...
Страница 18: ...Domestic Air Conditioner PCB 2 CN1 CN2 CN3 CN4 CN5 CN6 CN7 CN11 CN10 15 HSU12 18VHJ DB ...
Страница 21: ... Domestic Air Conditioner PCB 2 CN1 CN2 CN3 CN4 CN5 CN6 CN7 CN11 CN10 18 HSU12 18VHJ DB ...
Страница 94: ...9 3 1 Removal of Outdoor Panel 9 3 For 12 18K Outdoor unit Removal Procedure HSU12 18VHJ DB 91 ...
Страница 95: ...Loosen the top panel screws 1 2 Lift the top panel HSU12 18VHJ DB Removal Procedure 92 ...
Страница 96: ...Domestic air conditioner Removal Procedure Loosen the csrews and pull the panel HSU12 18VHJ DB 93 ...
Страница 97: ...9 3 2 Removal of Electrical Box HSU12 18VHJ DB Removal Procedure 94 ...
Страница 98: ...9 3 3 Removal of Fan and Fan Motor HSU12 18VHJ DB Removal Procedure 95 ...
Страница 99: ...2 Loosen the fixing screws and remove the motor HSU12 18VHJ DB Removal Procedure 96 ...
Страница 100: ...9 3 4 Removal of fan motor Bracket and Partition HSU12 18VHJ DB Removal Procedure 97 ...
Страница 101: ...and remove the reactor Loosen the screw HSU12 18VHJ DB Removal Procedure 98 ...
Страница 103: ...4 Remove the compre ssor and pipe assay 5 Remove the conden ser HSU12 18VHJ DB Removal Procedure 100 ...
Страница 104: ... SSHQGL SSHQGL 3LSLQJ LDJUDPV 68 9 101 ...
Страница 109: ...10 3 Circuit Diagrams 10 3 1 INDOORUNIT FOR12K Appendix HSU12 18VHJ DB 106 ...