CONNECT SERIES SERVICE MANUAL
29
ENGLISH
Troubleshooting
No
Yes
Yes
Yes
No
Completely
open the liquid
valve and
gas valve of
outdoor unit
Start
E3 protection
Check if the system low pressure
is lower than 7psi
Check if the liquid
valve and gas valve
of outdoor unit
open completely
Check if there
is leakage in
the pipeline
Yes
No
Reconnect wire
according to the
circuit diagram
or replace the
pressure switch
Check if the low pressure
switch and its wiring are
normal
Charge refrigerant
according to the
requirement and then
turn on the unit to see if
E3 protection still occurs
Yes
“E3” Compressor Low-
Pressure Protection,
Refrigerant Undercharge
Protection, Refrigerant
Recovery Mode
Error display:
ODU main board LED display
Error judgment condition
and method:
It is judged through the action
of low pressure switch. If the
low pressure switch is cut off,
it is judged that low pressure is
too low and the system stops
operation for protection.
Possible causes:
• Service valve of ODU is not
fully opened
• Low pressure sensor is
abnormal
• Outdoor or indoor fan is not
working properly
• IDU filter or air duct is
blocked (cooling mode)
• Ambient temperature is too
low
• System is undercharged
• Refrigerant line set is blocked
Weld the leakage
point and recharge
refrigerant after
vacuum pumping
and pressure
retaining are
passed
Replace the outdoor
main control board
Содержание GE Connect Series
Страница 17: ...CONNECT SERIES SERVICE MANUAL 15 ENGLISH Troubleshooting Model AUH4860ZGDA ...
Страница 28: ...CONNECT SERIES SERVICE MANUAL 26 ENGLISH Troubleshooting AUH4860ZGDAA ...
Страница 90: ...CONNECT SERIES SERVICE MANUAL 88 ENGLISH Maintenance AUH4860ZGDA ...
Страница 92: ...CONNECT SERIES SERVICE MANUAL 90 ENGLISH Maintenance IDU Exploded View and Parts Lists UUY24ZGDAA UUY36ZGDAA ...