CONNECT SERIES SERVICE MANUAL
13
ENGLISH
Controls
Forced Defrost Control
Press and hold the SW1 button for about 5 seconds to enter the first menu level. The outdoor unit main
board display will flash. Short-press the SW1 button to switch the function to “06”. Short-press SW2 or SW3
to change the selection within function “06” to “ON”, followed by a short-press on SW1 to save. The menu
will time out if no function is performed within 10 seconds.
Refrigerant Recovery Control
Press and hold the SW1 button for about 5 seconds to enter the first menu level. The outdoor unit main
board display will flash. Short-press the SW1 button to switch the function to “08”. Short-press SW2 or SW3
to change the selection within function “08” to “ON”, followed by a short-press on SW1 to save. The menu
will time out if no function is performed within 10 seconds.
Forced Operation
Press and hold “SW1” for about 5 seconds to enter the first level menu. The outdoor unit main board LED
display flashes. Under the first level menu, short press “SW1” to switch various functions. After switching to
“09”; short press “SW2” or “SW3” to enter the forced operation control mode. “01” denotes forced cooling
mode. “02” indicates forced heating mode. “OF” indicates shutdown of forced cooling / heating mode. Short
press ”SW1” to save. If no operation is performed within 10 seconds; the system will exit.
Query Functions
Long press “SW1” until display flashes. Short press “SW1” until “11” is displayed. Press “SW2” or “SW3” until
the desired Query is displayed. Press “SW1” to select. (If no operation is performed within 10 seconds; the
system will exit):
01 – Compressor Frequency in Hz
02 – Discharge Temperature in Celsius degrees
08 – Fan Rpm (speed is displayed with the last digit dropped (example 810 rpm will display as 81).
Содержание GE Connect Series
Страница 17: ...CONNECT SERIES SERVICE MANUAL 15 ENGLISH Troubleshooting Model AUH4860ZGDA ...
Страница 28: ...CONNECT SERIES SERVICE MANUAL 26 ENGLISH Troubleshooting AUH4860ZGDAA ...
Страница 90: ...CONNECT SERIES SERVICE MANUAL 88 ENGLISH Maintenance AUH4860ZGDA ...
Страница 92: ...CONNECT SERIES SERVICE MANUAL 90 ENGLISH Maintenance IDU Exploded View and Parts Lists UUY24ZGDAA UUY36ZGDAA ...