22
Electric wiring and the application
Power wiring fi gure
Outdoor power source and power cable
Please make sure that when the unit is running, the input voltage is no less than 380V;
if it is lower than 380V,the unit may run abnormal.
• Indoor and outdoor use their individual power source.
• All indoors use one power source.
• Must install the leakage breaker and the over current breaker, or electric shock will occur.
• Power cable must be
fi
xed
fi
rmly.
• Each outdoor must be earthed well.
• When power cable exceeds the range, thicken it appropriately.
power source: 3N~, 380-400V, 50/60Hz
power source: 3N~, 380-400V, 50/60Hz
power source: 3N~, 380-400V, 50/60Hz
power source: 3N~, 380-400V, 50/60Hz
power source: 3N~, 380-400V, 50/60Hz
power source: 3N~, 380-400V, 50/60Hz
Item
Model
Power
source
Power
cable
section
(mm
2
)
Wire
length
(m)
Circuit
breaker
(A)
Rated current of residual
circuit breaker(A)
Ground fault
interruptor(mA)
response time(S)
Ground wire
Section
(mm
2
)
Screw
Individual power
AV08NMSETA
3N~,
380-
400V,
50/60
Hz
2.5
60
16
40A 30mA below 0.1S
2
.5
M5
AV10NMSETA
2.5
60
16
40A 30mA below 0.1S
2.
5
M5
AV12NMSETA
2,5
60
16
40A 30mA below 0.1S
2
.5
M5