Installation procedure
3. Pipe "c" diameter (main pipe, between outdoor gather pipe and the
fi
rst branch pipe)
Outdoor capacity
(kW)
Main pipe
Enlarged main pipe
Gas pipe (mm)
Liquid pipe (mm)
Gas pipe (mm)
Liquid pipe (mm)
22.4
Ø22.22
Ø9.52
Ø22.22
Ø12.7
28.0
Ø22.22
Ø9.52
Ø25.4
Ø12.7
33.5
Ø25.4
Ø12.7
Ø28.58
Ø12.7
Note:
When the distance from outdoor to the longest indoor is over 90m, the main pipe should be
enlarged diameter.
Copper pipe selection:
Material
O type pipe: Soft pipe
Pipe diameter (mm)
Ø6.35
Ø9.52
Ø12.7
Ø15.88
Thickness(mm)
0.8
0.8
1.0
1.0
Material
Hard pipe
Pipe diameter (mm)
Ø19.05 Ø22.22
Ø25.4
Ø28.58
Ø31.8
Thickness(mm)
1.0
1.0
1.0
1.0
1.1
Long pipe and high drop
Model
Item
Outdoor
Single way total pipe length
300m
Single way pipe length
Max.: 150m (Equal Length 175m)
Main pipe beween outdoor to 1st branch
Max.: 110m (Equal Length 135m)
Pipe length between outdoors
Less than 10m to 1st branch pipe
Height difference between
indoor and outdoor
Outdoor is upper
Max. 50m
Outdoor is lower
Max. 40m
Height difference between outdoors
(in the same system)
Within 5m (better be horizontal)
Height difference between indoors
Max. 15m
1. Applicable range
Unit pipe spec and connection method (unit: mm)
A. Outdoor unit
Mobel
Gas pipe side
Liquid pipe side
Diameter
(mm)
Connecting method
Diameter
(mm)
Connecting method
AV08NMSETA
Ø19.05
Flared joint
Ø9.52
Flared joint and Brazing
AV10NMSETA
Ø22.22
Flared joint and Brazing
Ø12.7
Flared joint
AV12NMSETA
Ø25.4
Ø12.7