10.3.12 High work-intense protection
Outdoor display
LED1 flash 21 times
Method of
High work-intense control is activated in the heating mode if the temperature
Malfunction
being sensed by the heat exchanger thermistor exceeds the limit.
Detection
Malfunction
Activated when the temperature being sensed by the heat exchanger
Decision
rises above 65
℃
twices in 30 minutes.
Conditions
Supposed
■
Faulty electronic expansion valve
Causes
■
Dirty heat exchanger
■
Faulty heat-exchange sensor
■
Insufficient gas
Troubleshooting
* Caution Be sure to turn off power switch before connect or disconnect connector, or
else parts damage may be occurred.
Electrify the machine again and turn it on with the
remote controller, check whether the wind
temperature is below 65
℃
The malfunction is reported
after the machine has run
for some time?
1
、
Check room temperature and
pipe temperature sensor.
2
、
the temperature monitoring circuit
of the indoor mainboard
The indoor unit blows poorly
due to blocked filters or poor
condition of the fan?
1) Clean the filters
2) Reinstall the fan.
Use some tools to measure the pressure of system
,
YES
NO
YES
NO
Содержание AS50XCAHRA
Страница 12: ... Piping diagrams Domestic air conditioner 5ˊPiping diagrams 10 ...
Страница 14: ...Domestic air conditioner PCB 12 CN8 CN9 CN21 CN36 CN23 CN6 CN52 CN5 CN14 CN2 CN34 CN15 CN11 CN51 CN5 CN11 ...
Страница 27: ...Seivice diagnosis Domestic air conditioner 8 Dimensional drawings 9 Center of gravity unit mm 26 ...
Страница 43: ...Circuit diagrams Domestic air conditioner 41 11 2 Circuit Diagrams ...