Installations
Domestic air conditioner
10.3.11 Loss of synchronism detection
Inverter side current detection is abnormal
Outdoor Display LED1 flash 18 times
LED1 flash 19 times
Method of
The position of the compressor rotor can not detected normally
Malfunction
Detection
Malfunction
when the wiring of compressor is wrong or the connection is poor;
Decision
or the compressor is damaged
Conditions
Supposed
■
Faulty The wiring of compressor
Causes
■
Faulty compressor
■
Faulty PCB
Troubleshooting
* Caution Be sure to turn off power switch before connect or disconnect connector, or parts
damage may be occurred.
Within 3 minutes after the machine is
supplied with power and turned on with
the remote controller, check whether
the compressor can start up
1. The wiring of compressor is incorrect
or the connection is poor;
2. The compressor is damaged
At first, the compressor start up ,soon the
compressor stopped with the LED1 on the
outdoor PCB blinks
(
1Hz
)
19/18 times
IPM Module is damaged and needs
replacing.
the Malfunctions exist also, the
compressor is damaged replace a
new one
YES
NO
YES
Malfunction unsolved
Maybe there is some disturbance
38
Содержание AS50XCAHRA
Страница 12: ... Piping diagrams Domestic air conditioner 5ˊPiping diagrams 10 ...
Страница 14: ...Domestic air conditioner PCB 12 CN8 CN9 CN21 CN36 CN23 CN6 CN52 CN5 CN14 CN2 CN34 CN15 CN11 CN51 CN5 CN11 ...
Страница 27: ...Seivice diagnosis Domestic air conditioner 8 Dimensional drawings 9 Center of gravity unit mm 26 ...
Страница 43: ...Circuit diagrams Domestic air conditioner 41 11 2 Circuit Diagrams ...