Functions and Control
Domestic air conditioner
Control feature: send the dehumidifying signal to the outdoor system.
When Tr>Ts+2
℃
, the compressor will be turned on, the indoor fan will operate at the set speed.
When Tr is between the Ts and Ts+2
℃
, the outdoor system will operate at the high dehumidifying
frequency for 10 minutes and then at the low dehumidifying mode for six minutes. The indoor fan will
operate at low speed.
When Tr< Ts-1.5
℃
, the outsystem will be stopped, the indoor fan will be stopped for 3 minutes and then
turned to the low speed option.
All the frequency converses have a
±
1
℃
difference.
* Wind speed control: Automatic:
When Tr
≥
Ts+ 5
℃
, high speed.
When Ts+3
℃
≤
Tr< Ts+5
℃
, medium speed.
When Ts+2
℃
≤
Tr< Ts+3
℃
, low speed.
When Tr<Ts+2
℃
, light speed.
If the outdoor fan stopped, the indoor fan will be paused for 3 minutes.
If the outdoor fan stopped for more than 3 minutes and the outdoor system still operates, the system will
be changed into light speed mode.
When the airflow speed has no delay from the high to low switching, the speed should be delayed for 3
minutes (remain at high speed for 3 minutes.) before the next switch.
Manual: When the sensor is off or Tr< Ts+3
℃
, the manual operation can not be made. (obligatory
automatic operation.)
*Airgate location control: the location for the airgate can be set according to your needs.
*Defrosting function: preventing the frosting on the indoor heat exchanger (when cooling or
dehumidifying). When the compressor works continuously for 6 minutes and the temperature of the
indoor coils has been below 1
℃
for 10 seconds, the compressor will be stopped and the malfunction
will be recorded in the malfunction list. The indoor system will continue to run. When the temperature of
the indoor coil is raised to 9
℃
, the compressor will be restarted again (the requirement of 3 minutes’
delay should be satisfied.)
* Coil protection (synchronic overheating protection) are installed for the four directions latch
malfunctions when dehumidifying.
* Timing system on/off function.
* Dormant control functio
n.
Ts+20AD
(≈2℃)
Ts
(
COOL
)
(DRY)
3
(SHUT DOWN)
Ts-12AD
(≈1.5℃)
Ts+3AD
(≈0.5℃)
14
Содержание AS50XCAHRA
Страница 12: ... Piping diagrams Domestic air conditioner 5ˊPiping diagrams 10 ...
Страница 14: ...Domestic air conditioner PCB 12 CN8 CN9 CN21 CN36 CN23 CN6 CN52 CN5 CN14 CN2 CN34 CN15 CN11 CN51 CN5 CN11 ...
Страница 27: ...Seivice diagnosis Domestic air conditioner 8 Dimensional drawings 9 Center of gravity unit mm 26 ...
Страница 43: ...Circuit diagrams Domestic air conditioner 41 11 2 Circuit Diagrams ...