Installations
Domestic air conditioner
34
10.3.8 Power Supply Over or under voltage fault
Outdoor display: LED1 flash 6 times The power supply is over voltage
Method of
An abnormal voltage rise or fall is detected by checking the specified voltage detection circuit.
Malfunction
Detection
Malfunction
An voltage signal is fed from the voltage detection circuit to the microcomputer
Decision
Conditions
Supposed
■
Supply voltage not as specified
Causes
■
the IPM module is broken
■
the outdoor PCB is broken
Troubleshooting
* Caution Be sure to turn off power switch before connect or disconnect connector, or else
parts damage may be occurred.
Electrify the machine again and turn it on with
the remote controller. Check whether the
compressor is started normally
Is it ok?
Yes
Maybe there is some disturbance
NO
No
~230 is ok?
Yes
Yes
This question may be caused by the power. Repair
the power supply.
NO
Change the IPM module
Change the IPM module
Test the outdoor power supply
(+310VDC) with a multimeter.
check whether the power
is >150 V or <390V?
Содержание AS50XCAHRA
Страница 12: ... Piping diagrams Domestic air conditioner 5ˊPiping diagrams 10 ...
Страница 14: ...Domestic air conditioner PCB 12 CN8 CN9 CN21 CN36 CN23 CN6 CN52 CN5 CN14 CN2 CN34 CN15 CN11 CN51 CN5 CN11 ...
Страница 27: ...Seivice diagnosis Domestic air conditioner 8 Dimensional drawings 9 Center of gravity unit mm 26 ...
Страница 43: ...Circuit diagrams Domestic air conditioner 41 11 2 Circuit Diagrams ...