Installations
Domestic air conditioner
31
Check whether Terminal on the outdoor
mainboard is well inserted.
it is normal
Reinsert the terminals
Electrify the machine again and turn it on in
the Cool state with the remote controller.
check whether the motor could run
.
Remove fan motor after s witch off
the power.
Measure the resistances
between black line (0V) and red
line( 310V),between black line(0V)
and white line (15V) of the fan
motor .
NO
YES
The resistances are
greater than 40K
Ω
NO
YES
The motor of the outdoor unit is
damaged and needs replacing.
NO
the resistances between 0V
and 310V,between 0V and 15V of
the fan terminal of outdoor pcb are
greater than 10M
Ω
.
The module pcb is
damaged, replace it
with a new one.
The
outdoor pcb
is
damaged, replace it
with a new one.
YES
The motor and
outdoor pcb are
well
YES
NO
10.3.5 IPM protection
Outdoor display: LED1 flash 2 times
Method of
IPM protection is detected by checking the compressor running condition and so on
Malfunction
Detection
Malfunction
■
The system leads to IPM protection due to over current
Decision
■
The compressor faulty leads to IPM protection
Conditions
■
circuit component of IPM is broken and led to IPM protection
Содержание AS50XCAHRA
Страница 12: ... Piping diagrams Domestic air conditioner 5ˊPiping diagrams 10 ...
Страница 14: ...Domestic air conditioner PCB 12 CN8 CN9 CN21 CN36 CN23 CN6 CN52 CN5 CN14 CN2 CN34 CN15 CN11 CN51 CN5 CN11 ...
Страница 27: ...Seivice diagnosis Domestic air conditioner 8 Dimensional drawings 9 Center of gravity unit mm 26 ...
Страница 43: ...Circuit diagrams Domestic air conditioner 41 11 2 Circuit Diagrams ...