Page 56
SIA CP-01 COMPLIANCE
This control complies with the SIA CP-01 Control Panel Standard - Features for False Alarm Reduction.
CP-01 is a standard sponsored by the Security Industry Association (SIA) designed with features for security systems and
associated arming and disarming devices intended to reduce the incidence of false alarms.
PROGRAMMABLE FEATURES
SHIPPING DEFAULTS AND RECOMMENDED PROGRAMMING
FEATURE
CP-01
PAR. #
REQUIREMENT
RANGE
SHIPPING
DEFAULT
RECOMMENDED
PROGRAMMING*
Exit Time
(Exit Delay)
4.2.2.1 Required
(programmable)
For full or auto arming: 45-180
seconds
60 seconds
60 seconds
Progress Annunciation - Disable
(Audible Exit Delay)
4.2.2.2
Allowed
Individual consoles may be
disabled
Enabled on
all consoles
Enabled on all consoles
Exit Time Restart
4.2.2.3
Required Option
For re-entry during exit delay
Enabled
Enabled
Unvacated Premises
4.2.2.5 Required
Option
(except for remote arm)
If no exit after full arm Enabled
Enabled
Entry Delay
4.2.3.1
Required
(programmable)
30-60 seconds
30 seconds
At least 30 seconds**
Abort Window for Non-Fire Zones
(Dial Out Delay – Zone Option)
4.2.5.1
Required Option
May be disabled by zone
Enabled
Enabled (all zones)
Abort Window Time
(Dial Out Delay)
4.2.5.1
Required Option
15-45 seconds
30 seconds
At least 15 seconds**
Abort annunciation
(Alarm Aborted)
4.2.5.1.2
Required Option
Display that alarm was aborted
Enabled
No programming option
Cancel annunciation
(Alarm Canceled)
4.2.5.4.1
Required Option
Display that alarm was canceled
Enabled
No programming option
Duress Feature
(Duress Code)
4.2.6.1 &
4.2.6.2
Allowed Option
No duplicates with other user codes
Disabled
Disabled
Cross Zoning
(Cross Zoning – Zone Option)
4.3.1
Required Option
May be enabled by zone
Disabled
Enabled and two (or
more) zones programmed
Programmable Cross Zoning Time
(Cross Zone Window)
4.3.1
Allowed
15-120 seconds
15 seconds
Time based on walk path
in protected area
Swinger Shutdown
(Swinger Shutdown Number)
4.3.2 Required
(programmable)
For all non-fire zones, shut down at
1 or 2 trips
One trip
One trip
Swinger Shutdown Disable
(Swinger Shutdown – Zone Option)
4.3.2
Allowed
For non-police response zones
Enabled
Enabled (all zones)
Fire Alarm Verification
4.3.3
Required Option
Depends on Sensors
Disabled
Enabled unless sensor
can self verify
Call Waiting Cancel
4.5
Required Option
Depends on user phone line
Disabled
Enabled if user has call
waiting
* Programmable at installation may be subordinate to other UL requirements for the intended application.
** Combined Entry Delay and Abort Window (Dial Out Delay) should not exceed 1 minute.