TWO-WIRE SMOKE DETECTORS
Omni IIe supports two-wire smoke detectors connected to Zones 1-4.
1.
Use normally open (closed for alarm) two-wire "SYSTEM" type smoke detectors (
See -
2-Wire Smoke Detector
Compatibility Chart).
2.
Smoke detectors must be connected to Zones 1-4 and configured as a Supervised Fire Zone.
3.
An external 1000-ohm end-of-line resistor must be used.
4.
Connect to the SWITCH 12V or an Output configured as a SWITCHED POWER OUTPUT.
5.
The corresponding Zone Jumpers (JP11-JP14) must be in the SMK (smoke) position.
4.
Refer to
FIGURE 3 (TWO-WIRE FIRE ZONE CONNECTIONS)
for this configuration.
Smoke detector compatibility identifier: A
Detector Models
Detector Manufacturer
Maximum Detectors/Zone
2W-B
2WT-B
System Sensor, Unincorporated Div. of Honeywell International Inc.
10
DS260
DS282
DS282S
DS282TH
DS282THS
DS250
DS250TH
Bosch Security Systems
10
F220-P
F220-PTH
F220-PTHC
DS230
DS230F
Bosch Security Systems
8
429AT
521B (SW 1 “ON”)
521BXT (SW 1 “ON”)
521NB (6V)
521NBXT (6V)
GE Security Inc.
10
2-Wire Smoke Detector Compatibility Chart
FOUR-WIRE SMOKE DETECTORS
Omni IIe supports four-wire smoke detectors connected to any zone (1-48).
1.
Use normally open (closed for alarm) four-wire "SYSTEM" type smoke detectors (System Sensor 2112/24TR or equivalent),
rated 8 - 14 VDC.
2.
An End of Line Power Supervision Relay Module (System Sensor A77-716B or equivalent) is required for UL installations.
Install 1000-ohm end-of-line resistor as shown.
3.
Power the smoke detector from SWITCH 12V or an Output configured as a SWITCHED POWER OUTPUT.
4.
When connected to Zones 1-4, the appropriate Zone Jumper (JP11-JP14) must be in the SMK (smoke) position.
NOTE:
Smoke detectors connected to Zones 1-4 are wired differently from those connected to Zones 5-48.
Refer to
FIGURE 4 (FOUR-WIRE FIRE ZONE CONNECTIONS)
for each configuration.