Page 50
ARMING CONFIRMATION
The Arming Confirmation is a quick pulse (squawk) given by the outside siren when the alarm system is armed into a security
mode and the EXIT DELAY is expired.
ARMING CONFIRMATION: 0
0=NO 1=YES
To enable the arming confirmation feature, press the 1 (YES) key, then press the ' # ' key. The default setting is 0 (NO) disabled.
FIRE ALARM VERIFICATION
This unit is equipped with a FIRE ALARM VERIFICATION feature. When enabled, if a zone configured as a FIRE (Type 32)
or a GAS (Type 34) is activated, the system will cycle SWITCH 12V and Switched Power Outputs off for 10 seconds. The
SWITCH 12V power output will then be restored, and 5 seconds later, the zones will be monitored again. If the zone is activated
again within a 2-minute window, the fire alarm will be activated. If not, no fire alarm will be indicated.
VERIFY FIRE ALARMS: 0
0=NO 1=YES
This feature is turned OFF by factory default.
If VERIFY FIRE ALARMS is turned ON:
1)
Any
device (other than FIRE or GAS) connected to a SWITCH 12V Output (i.e. Glassbreak Detectors), must be
connected to a zone configured as a LATCHING ZONE TYPE.
2)
The following notice is required by UL:
WARNING
This unit includes an alarm verification feature that will result in a delay of the system fire alarm signal from the initiating
circuit. The total delay (Omni IIe controller plus detector delay) shall not exceed 60 seconds. No other initiating devices shall
be connected to these circuits unless approved by the local authority having jurisdiction.
Zone Control Detector Total Delay
Circuit Unit Delay Model/Delay
________ : 10 seconds + ______________ = __________________
________ : 10 seconds + ______________ = __________________
________ : 10 seconds + ______________ = __________________
________ : 10 seconds + ______________ = __________________
SUPERVISE INT SNDR
This enables or disables supervision of the Interior Horn Output, which monitors the wiring to the connected sirens. Factory
default is disabled.
SUPERVISE INT SNDR: 0
0=NO 1=YES
SUPERVISE EXT SNDR
This enables or disables supervision of the Exterior Horn Output, which monitors the wiring to the connected sirens. Factory
default is disabled.
SUPERVISE EXT SNDR: 0
0=NO 1=YES