background image

6LE007315Ab

3

 

 
 

HXA021H

AX contact

230 Vac

HXA014H

UV coil

230 Vac

4

 2

1

1

HXA021H

AX contact

230 Vac

4

1

HXA024H

AL contact

230 Vac

4

HXA014H

UV coil

230 Vac

 
 

1

2

L1
L2
L3
N

L1
L2
L3
N

230/400 V

230/400 V

mechanical

interlock

HX

x

042H

MCCB 1

MCCB 2

P1 OFF ON C P2 E

Motor 1

230 Vac

supply

electrical

interlock

11 14 12

21 24 22

31 34 32

41 44 42

51 54 52

61 64 62

71 72 73 74 75 76 70 82 81

OUT 1

OUT 2

OUT 3

OUT 4

OUT 5

OUT 6

USB

IN1 IN2 IN3 IN4 IN5 IN6 COM + -

INPUTS

N

SOURCE 1 

    L3  

  

L2     L1

N

SOURCE 2 

    L3  

  

L2     L1

RS485

NC - +

HX

x

042H

P1 OFF ON C P2 E

Motor 2

230 Vac

supply

emergency

stop

1 A

1 A

ESC427

ESC427

ESC427

ESC126

6 A

6 A

HZI855 with MCCB
for network / network application type

 

 
 

HXA021H

AX contact

230 Vac

HXA014H

UV coil

230 Vac

4

 2

1

1

HXA021H

AX contact

230 Vac

4

1

HXA024H

AL contact

230 Vac

4

HXA014H

UV coil

230 Vac

 
 

1

2

L1
L2
L3

N

L1
L2
L3

N

230/400 V

230/400 V

mechanical

interlock

HX

x

042H

MCCB 1

MCCB 2

P1 OFF ON C P2 E

Motor 1

230 Vac

supply

electrical

interlock

11 14 12

21 24 22

31 34 32

41 44 42

51 54 52

61 64 62

71 72 73 74 75 76 70 82 81

OUT 1

OUT 2

OUT 3

OUT 4

OUT 5

OUT 6

USB

IN1 IN2 IN3 IN4 IN5 IN6 COM + -

INPUTS

N

SOURCE 1 

    L3  

  

L2     L1

N

SOURCE 2 

    L3  

  

L2     L1

RS485

NC - +

HX

x

042H

P1 OFF ON C P2 E

Motor 2

230 Vac

supply

emergency

stop

1 A

1 A

ESC427

ESC427

GE

Start 

6 A

6 A

HZI855 with MCCB
for network / genset application type

Note: indicated references are used for MCCB x250/P250 and x630/P630.

Default configuration for Inputs and Outputs for "Breaker" mode:

IN1: Breaker 1 is in position ON
IN2: Breaker 2 is in position ON
IN3: Breaker 1 is in position OFF
IN4: Breaker 2 is in position OFF
IN5: Breaker 1 is in position TRIP
IN6: Emergency stop
OUT1: Order to close Breaker 1
OUT2: Order to close Breaker 2
OUT3: Order to open Breaker 1
OUT4: Order to open Breaker 2
OUT5: NONE
OUT6: Order to start Genset

This configuration is defined with source I as the priority source.

This diagram covers most application cases, the inputs and outputs 

are configured by default for this installation, the actions of the 

controller will be:

- In the event of neutral loss from source I: the undervoltage coil 

will trip the circuit breaker for source I making it unavailable (ALarm 

contact on input 5) to switch to secondary source II.

- In the event of tripping via the emergency stop button: the 

undervoltage coil will trip the circuit breaker of the source I making it 

unavailable (ALarm contact on input 5) BUT the control ler will switch 

to " total inhibition ”(input 6 activated), that is to say that the load will 

no longer be supplied without manual intervention on the controller in 

order to acknowledge this fault.

After acknowledgment, the controller will switch to priority source I if 

available, otherwise to secondary source II.