There are several events that can cause a Fault on the controller. Unlike the alarms, the faults are not user-selectable, they will 

always be considered and actions will take place as follows:

FAULT

DESCRIPTION (CAUSE)

ACTIONS

ACKNOWLEDGE / 

CLEARED

FAULT 

LOG

POP-UP

FAULT LED

OUTPUT

Unexpected 

Transfer

The controller receives a 

feedback/return from the 

switch without sending any 

order (auto or manu). Also 

if loss feedback of current 

position.

Mode stays the 

same. Controller 

will start retries if 

position is unknown. 

If a position is 

reached, no retry 

takes place. 

Can also be cleared 

through display or 

through RST - Reset 

Fault input.

Yes

Yes, "Unexpected 

Transfer"

BLINKS 

(priority)

FLT - Fault active

Failed to Transfer

Position not reached after 

an order sent by controller 

(auto or manu) or loss of 

feedback of the new source 

after sending a transfer 

command.

Mode stays the 

same. Controller will 

start retries.

Automatically cleared 

if the requested 

position is reached 

or cleared through 

display or through 

RST - Reset Fault 

input.

Yes

Yes, "Failed to 

transfer"

BLINKS 

(priority)

FLT - Fault active

Max operation per 

minutes reached

If the controller performs 

10 operations in less 

than 1 minute (by default) 

(automatic or controlled/

manual)

Mode stays the 

same. During a timer, 

the controller will 

not do or allow any 

operation.

Automatic after the 1 

minute (configurable 

through software)

(value is dynamic).

Yes

Yes, "Max 

operations per 

minutes reached"

FIXED 

(non-critical)

FLT - Fault active

Max password 

attempts reached

User tries to enter a profile 

password more than X times 

set in the maintenance menu 

(by default 10 attempts)

Mode stays the 

same. Can't enter 

any password 

during X time set 

in the maintenance 

menu (by default 2 

minutes)

Automatic after 

the set timeout 

(maintenance mode).

Yes

Yes, "Max number 

of tries reached, 

please wait: X s"

FIXED 

(non-critical)

FLT - Fault active

Genset Failstart

Controller tries to start a 

genset (as configured) and 

after the genset start delay, 

the genset doesn't start 

(controller doesn't see the 

source on)

Mode stays the 

same. Genset start 

relay remains active 

unless other source 

is available.

Automatic if genset 

starts or if source is 

set as Main/Utility. 

Yes

Yes, "Engine fail to 

start"

BLINKS 

(priority)

FLT - Fault active

External fault

If an input is selected as 

FTE - External Fault and 

becomes active

Switch goes to 

position 0 /center-

off directly without 

timers and the mode 

is set to Partial 

Inhibit (genset starts 

if needed).

Input mustn't be 

active and reset by 

user is requested 

(by RST- Reset Fault 

input or through 

display.

Yes

Yes, "External 

fault"

BLINKS 

(priority)

FLT - Fault active

For faults with pop-up, the pop-up will be cleared when fault will be cleared or by pressing any button on the front face of the 
controller. The total number of faults logged on the controller is dynamic, as the total number of “ alarms” is 100 (not 
including the events, which are 300) and uses a FIFO ordering.

To clear Faults through the display, it is possible inside the LOG/FAULTS menu with the option “PRESS OK TO CLEAR 

FAULTS”, using the configurator profile password (1000). There is also a shortcut by holding the 

 button for 1.5s and 

validating on the pop-up that appears. If the fault is still active, it will be inside the log “in progress” but the fault LED and 
output will be off. If the faults are not active any more, they will be logged in the “history” log. This way to clear the fault will 

be automatically proposed by the controller through a pop-up:

Trouble shooting guide

FAULTS

FAILED TO TRANSFER

1,5 s -> RESET FAULTS