There are several events that can cause a Fault on the controller. Unlike the alarms, the faults are not user-selectable, they will
always be considered and actions will take place as follows:
FAULT
DESCRIPTION (CAUSE)
ACTIONS
ACKNOWLEDGE /
CLEARED
FAULT
LOG
POP-UP
FAULT LED
OUTPUT
Unexpected
Transfer
The controller receives a
feedback/return from the
switch without sending any
order (auto or manu). Also
if loss feedback of current
position.
Mode stays the
same. Controller
will start retries if
position is unknown.
If a position is
reached, no retry
takes place.
Can also be cleared
through display or
through RST - Reset
Fault input.
Yes
Yes, "Unexpected
Transfer"
BLINKS
(priority)
FLT - Fault active
Failed to Transfer
Position not reached after
an order sent by controller
(auto or manu) or loss of
feedback of the new source
after sending a transfer
command.
Mode stays the
same. Controller will
start retries.
Automatically cleared
if the requested
position is reached
or cleared through
display or through
RST - Reset Fault
input.
Yes
Yes, "Failed to
transfer"
BLINKS
(priority)
FLT - Fault active
Max operation per
minutes reached
If the controller performs
10 operations in less
than 1 minute (by default)
(automatic or controlled/
manual)
Mode stays the
same. During a timer,
the controller will
not do or allow any
operation.
Automatic after the 1
minute (configurable
through software)
(value is dynamic).
Yes
Yes, "Max
operations per
minutes reached"
FIXED
(non-critical)
FLT - Fault active
Max password
attempts reached
User tries to enter a profile
password more than X times
set in the maintenance menu
(by default 10 attempts)
Mode stays the
same. Can't enter
any password
during X time set
in the maintenance
menu (by default 2
minutes)
Automatic after
the set timeout
(maintenance mode).
Yes
Yes, "Max number
of tries reached,
please wait: X s"
FIXED
(non-critical)
FLT - Fault active
Genset Failstart
Controller tries to start a
genset (as configured) and
after the genset start delay,
the genset doesn't start
(controller doesn't see the
source on)
Mode stays the
same. Genset start
relay remains active
unless other source
is available.
Automatic if genset
starts or if source is
set as Main/Utility.
Yes
Yes, "Engine fail to
start"
BLINKS
(priority)
FLT - Fault active
External fault
If an input is selected as
FTE - External Fault and
becomes active
Switch goes to
position 0 /center-
off directly without
timers and the mode
is set to Partial
Inhibit (genset starts
if needed).
Input mustn't be
active and reset by
user is requested
(by RST- Reset Fault
input or through
display.
Yes
Yes, "External
fault"
BLINKS
(priority)
FLT - Fault active
For faults with pop-up, the pop-up will be cleared when fault will be cleared or by pressing any button on the front face of the
controller. The total number of faults logged on the controller is dynamic, as the total number of “ alarms” is 100 (not
including the events, which are 300) and uses a FIFO ordering.
To clear Faults through the display, it is possible inside the LOG/FAULTS menu with the option “PRESS OK TO CLEAR
FAULTS”, using the configurator profile password (1000). There is also a shortcut by holding the
button for 1.5s and
validating on the pop-up that appears. If the fault is still active, it will be inside the log “in progress” but the fault LED and
output will be off. If the faults are not active any more, they will be logged in the “history” log. This way to clear the fault will
be automatically proposed by the controller through a pop-up:
Trouble shooting guide
FAULTS
FAILED TO TRANSFER
1,5 s -> RESET FAULTS