hager HZI855 Скачать руководство пользователя страница 2

3P + N

1P + N

2P + N

2P

3P

L1

L2

L1

L2

L3

L1

L2

L1

L2

L3

N

L1

N

N

6LE007315Ab

2

1

60

2

20

240

64

49

180

Type of networks

Metering and sensing detail

Networks

mm

Loss of neutral: will be detected in all cases except 

for balanced networks with balanced loads.

In Breaker mode: the use of undervoltage release 

(see wiring diagram) can prevent this situation.

Power Supply:

The HZI855 controller is Self-powered from the voltage sensing of any 
available source, and may also be powered (as a backup from saved 
source) from the DC auxiliary power input (24 VDC). 

Dual  Power  Supply / Sensing
The HZI855 controller will be automatically supplied from the voltage 
sensing connectors of both sources thanks to an internal DPS (dual power 
supply) module that in case main source failure, will immediately switch to 
the secondary source supply the device.

NOTE:

 The nominal auxiliary power supply feeding the sensing terminals 

must be within the limits of 88 

 576 VAC.

NOTE: The HZI855 must include a SCPD such 

as fuses on each phase of the voltage sensing 

control wiring.

1A gG fuses are recommended.

NETWORK TYPE

1P+N

2P

2P+N

3P

3P+N

3P+N / 1P+N

Source

 

1

1 phase

2 wire

2 phase

2 wire

2 phase

3 wire

3 phase

3 wire

3 phase

4 wire

3 phase

4 wire

Source

 

2

1 phase

2 wire

301 302 201202

101

HZI812

102

L

N

L

N

L

N

4 A

4 A

 
 

1

2

L1
L2
L3
N

L1
L2
L3
N

230/400 

V

230/400 

V

HIB4xxM

11 14 12

21 24 22

31 34 32

41 44 42

51 54 52

61 64 62

71 72 73 74 75 76 70 82 81

OUT 1

OUT 2

OUT 3

OUT 4

OUT 5

OUT 6

USB

IN1 IN2 IN3 IN4 IN5 IN6 COM + -

INPUTS

N

SOURCE 1 

    L3  

  

L2     L1

N

SOURCE 2 

    L3  

  

L2     L1

RS485

NC - +

312 313 314 315 316 317 63A64A 24 14 04 13

Ctrl OFF

I I

I I

I

I

0

0

C

C

30

13

02

1 A

1 A

*

Dimensions

HZI855 and HIB4xxM
for network / network application type

for network / genset application type

301302 201 202

101

HZI812

102

L

N

L

N

L

N

4 A

4 A

 
 

1

L1
L2
L3
N

L1
L2
L3
N

230/400 V

230/400 V

HIB4xxM

11 14 12

21 24 22

31 34 32

41 44 42

51 54 52

61 64 62

71 72 73 74 75 76 70 82 81

OUT 1

OUT 2

OUT 3

OUT 4

OUT 5

OUT 6

USB

IN1 IN2 IN3 IN4 IN5 IN6 COM + -

INPUTS

N

SOURCE 1 

    L3  

  

L2     L1

N

SOURCE 2 

    L3  

  

L2     L1

RS485

NC - +

312 313 314 315 316 317 63A64A 24 14 04 13

Ctrl OFF

I I

I I

I

I

0

0

C

C

30

13

02

1 A

1 A

GE

Start 

*

Default configuration for Inputs and Outputs for "HIB4xxM" mode:

IN1: Switch is in position 1

IN2: Switch is in position 2

IN3: Switch is in position 0

IN4: Inhibit

IN5: Manual restransfer

IN6: RTSE in manual

OUT1: Order to switch in position 1

OUT2: Order to switch in position 2

OUT3: Order to switch in position 0

OUT4: S1 Available

OUT5: S2 Available

OUT6: Order to start Genset

* The use of this input is optional, when used IN6 should be configured 

to "COVER OPEN" in mode "NC".

This configuration is defined with source I as the priority source.

This diagram covers most application cases, the inputs and outputs 

are configured by default for this installation.

For single phase networks, 
the neutral has to be 
bridged from N to L2