3P + N
1P + N
2P + N
2P
3P
L1
L2
L1
L2
L3
L1
L2
L1
L2
L3
N
L1
N
N
6LE007315Ab
2
1
60
2
20
240
64
49
180
Type of networks
Metering and sensing detail
Networks
mm
Loss of neutral: will be detected in all cases except
for balanced networks with balanced loads.
In Breaker mode: the use of undervoltage release
(see wiring diagram) can prevent this situation.
Power Supply:
The HZI855 controller is Self-powered from the voltage sensing of any
available source, and may also be powered (as a backup from saved
source) from the DC auxiliary power input (24 VDC).
Dual Power Supply / Sensing
The HZI855 controller will be automatically supplied from the voltage
sensing connectors of both sources thanks to an internal DPS (dual power
supply) module that in case main source failure, will immediately switch to
the secondary source supply the device.
NOTE:
The nominal auxiliary power supply feeding the sensing terminals
must be within the limits of 88
➡
576 VAC.
NOTE: The HZI855 must include a SCPD such
as fuses on each phase of the voltage sensing
control wiring.
1A gG fuses are recommended.
NETWORK TYPE
1P+N
2P
2P+N
3P
3P+N
3P+N / 1P+N
Source
1
1 phase
2 wire
2 phase
2 wire
2 phase
3 wire
3 phase
3 wire
3 phase
4 wire
3 phase
4 wire
Source
2
1 phase
2 wire
301 302 201202
101
HZI812
102
L
N
L
N
L
N
4 A
4 A
1
2
L1
L2
L3
N
L1
L2
L3
N
230/400
V
230/400
V
HIB4xxM
11 14 12
21 24 22
31 34 32
41 44 42
51 54 52
61 64 62
71 72 73 74 75 76 70 82 81
OUT 1
OUT 2
OUT 3
OUT 4
OUT 5
OUT 6
USB
IN1 IN2 IN3 IN4 IN5 IN6 COM + -
INPUTS
N
SOURCE 1
L3
L2 L1
N
SOURCE 2
L3
L2 L1
RS485
NC - +
312 313 314 315 316 317 63A64A 24 14 04 13
Ctrl OFF
I I
I I
I
I
0
0
C
C
30
13
02
1 A
1 A
*
Dimensions
HZI855 and HIB4xxM
for network / network application type
for network / genset application type
301302 201 202
101
HZI812
102
L
N
L
N
L
N
4 A
4 A
1
L1
L2
L3
N
L1
L2
L3
N
230/400 V
230/400 V
HIB4xxM
11 14 12
21 24 22
31 34 32
41 44 42
51 54 52
61 64 62
71 72 73 74 75 76 70 82 81
OUT 1
OUT 2
OUT 3
OUT 4
OUT 5
OUT 6
USB
IN1 IN2 IN3 IN4 IN5 IN6 COM + -
INPUTS
N
SOURCE 1
L3
L2 L1
N
SOURCE 2
L3
L2 L1
RS485
NC - +
312 313 314 315 316 317 63A64A 24 14 04 13
Ctrl OFF
I I
I I
I
I
0
0
C
C
30
13
02
1 A
1 A
GE
Start
*
Default configuration for Inputs and Outputs for "HIB4xxM" mode:
IN1: Switch is in position 1
IN2: Switch is in position 2
IN3: Switch is in position 0
IN4: Inhibit
IN5: Manual restransfer
IN6: RTSE in manual
OUT1: Order to switch in position 1
OUT2: Order to switch in position 2
OUT3: Order to switch in position 0
OUT4: S1 Available
OUT5: S2 Available
OUT6: Order to start Genset
* The use of this input is optional, when used IN6 should be configured
to "COVER OPEN" in mode "NC".
This configuration is defined with source I as the priority source.
This diagram covers most application cases, the inputs and outputs
are configured by default for this installation.
For single phase networks,
the neutral has to be
bridged from N to L2