65
6LE005550A
Function of the Energy trip unit
3.4 Managing alarms and logs
Symbol
Meaning
S1
Activation value
T1
Activation time delay
T2
Deactivation time delay
Managing time delays
The time delays of customisable alarms are managed by 2 counters which are
normally at 0
For the activation time delay, the counter:
- Is increased when the activation condition is met
- Is decreased if the activation condition is not met and if the
time delay is not reached
- Is reset when the time delay is reached
For the deactivation time delay, the counter:
- Is increased when the deactivation condition is met
- Is decreased if the deactivation condition is no longer met and if the
time delay is not reached
- Is reset when the time delay is reached
When the activation time delay is reached, the alarm is activated.
When an alarm is reconfigured, the counters are also reset.
Example:
In this example, the alarm is set to a positive breach of the activation threshold
of 280 V when measuring the voltage V1N. The activation time delay is set at
4 seconds. The deactivation threshold is set at 250 V and the deactivation time
delay at 2 seconds.
S1: 280 V
S2: 250 V
T1: 4 s
T1 = 4 s
T2 = 2 s
T2: 2 s
t
t
t
ON
OFF
OFF
Customisable alarms: Time delays
Содержание h3+
Страница 1: ...Moulded Case Circuit Breakers up to 250 A h3 Communication System manual...
Страница 2: ...2 6LE005550A...
Страница 4: ...4 6LE005550A...
Страница 5: ...5 6LE005550A About this manual Page 1 1 Safety advice 6 1 2 Using this manual 8 1 3 Abbreviations 9...
Страница 10: ......
Страница 116: ...116 6LE005550A...
Страница 124: ...124 6LE005550A...
Страница 125: ...125 6LE005550A Support Page 6 1 Troubleshooting 126...
Страница 127: ...127 6LE005550A...