103
6LE005550A
Starting, commissioning, operation
4.6 Start-up and configuration via the HTD210H display
Description of an alarm notification
Display
Description
Trip alarm
Custom alarm
Appears when the active alarm has been assigned to the OAC
output contact. This indicates that the OAC contact has been
activated. The OAC contact can be assigned to one of the
12 custom alarms, the PTA pre-alarm or to a system alarm
(internal trip unit error, trip unit temperature alarm, rupture of
the neutral pole).
Example of an alarm notification
Display
Description
PTA overload pre-alarm
Appears when the circuit breaker load current has reached
the pre-trip warning zone, defined by the PTA setting.
Manual trip test
A manual trip test took place on 06/03/2018 at 2:35 p.m.,
and was performed via the HTP610H configuration tool.
Custom alarm no.1
Took place on 06/03/2018 at 2:18 p.m., voltage on phase 2 V2
> 240 V
Clearing an alarm notification
High priority alarm notifications must be cleared.
To clear high priority alarms:
Action
Key
1
Clear the alarm
- The notification
disappears.
Comment
After clearing, the alarm may still be active if the cause has not been eliminated.
In this case, the alarm window may be visible on the list of active alarms.
Содержание h3+
Страница 1: ...Moulded Case Circuit Breakers up to 250 A h3 Communication System manual...
Страница 2: ...2 6LE005550A...
Страница 4: ...4 6LE005550A...
Страница 5: ...5 6LE005550A About this manual Page 1 1 Safety advice 6 1 2 Using this manual 8 1 3 Abbreviations 9...
Страница 10: ......
Страница 116: ...116 6LE005550A...
Страница 124: ...124 6LE005550A...
Страница 125: ...125 6LE005550A Support Page 6 1 Troubleshooting 126...
Страница 127: ...127 6LE005550A...