![hager h3+ Скачать руководство пользователя страница 43](http://html2.mh-extra.com/html/hager/h3/h3_communication-instruction-manual_4861589043.webp)
43
6LE005550A
Function of the Energy trip unit
3.3 Measurement function
Electrical variable
Symbol used
Version
3 P
Version
4 P
Ground RMS (three-phase system
without neutral)
IG
X
–
RMS voltage
V1N, V2N, V3N
–
X
RMS voltage
U12, U23, U31
X
X
Phase rotation
1,2,3; 1,3,2
X
X
Frequency
f
X
X
In addition, the Energy trip unit calculates the following associated electrical
variables in real-time (every second):
Electrical variable
Variable calculation
Version
3 P
Version
4 P
Average RMS current
X
X
Maximum instantaneous RMS
current with neutral
–
X
Maximum instantaneous RMS
current without neutral
X
-
Minimum instantaneous RMS
current
X
X
Average Ph-N RMS voltage
–
X
Maximum Ph-N RMS voltage
–
X
Minimum Ph-N RMS voltage
–
X
Average Ph-Ph RMS voltage
X
X
Maximum Ph-Ph RMS voltage
X
X
Minimum Ph-Ph RMS voltage
X
X