Cable cooling tower
18
Technical changes reserved
For enclosures with 90 minutes fire resistance FBxxSE (not necessary for
FBxxLE) a so-called cable cooling tower must be mounted over the cable
bulkheads of the corresponding housing!
The cable cooling attachment is screwed with 2 angles on the housing and on
the wall.
For mounting on the wall, one dowel is used for each angle. To select the
Dowels, please refer to the information in the chapter
Assembly
of this manual.
For mounting on the housing/cable cooling attachment, 2 screws 4.5x35 are
used for each angle.
The cable cooling tower needs to be filled with mineral wool (included in the
delivery), which has a melting point > 1000°.
Angle bracket (2x) for cable cooling tower when mounted on top of the fire protection
housing.
Angle bracket (4x) for cable cooling tower when mounted below the fire protecting
housing.
8
Cable cooling tower
Содержание FB LE Series
Страница 1: ...Brandschutzgeh use Stand Wandmontage FBxxLE FBxxSE Montage und Bedienungsanleitung...
Страница 21: ...L fter Einheit anschlie en Technische nderungen vorbehalten 21 10 1 L fter Einheit Anschlussplan...
Страница 26: ...Befestigungssystem 26 Technische nderungen vorbehalten Einbauma e f r 1 feldigen Schrank...
Страница 27: ...Befestigungssystem Technische nderungen vorbehalten 27 Einbauma e f r 2 feldigen Schrank...
Страница 30: ...Fire Protection Enclosure FBxxLE FBxxSE Installation and Operation Instructions...
Страница 48: ...Ventilation diagram Technical changes reserved 19 Schematic diagram of the ventilation 9 Ventilation diagram...
Страница 50: ...Fan unit Connection Technical changes reserved 21 10 1 Fan unit Wiring diagram...
Страница 55: ...Fixing system 26 Technical changes reserved Assembly dimensions for 1 field enclosure...
Страница 56: ...Fixing system Technical changes reserved 27 Assembly dimensions for 2 field enclosure...