For your safety
Technical changes reserved
7
General information
-
Do not install any damaged parts – the guarantee and the proof of usability
shall be immediately invalidated.
-
Without complete and proper installation, the housing does not have the
proof of suitability in accordance with the building authorities.
-
The laws and directives of building legislation and the requirements of the
responsible building authority and the assigned fire protection expert must be
complied with.
-
As the installation technician, do not create an unrestricted manufacturer
declaration of compliance with the building authority approval unless
everything has been installed accordingly. Note any deviations which are not
negligible.
-
Please comply with the applicable VDE regulations.
-
Comply with the requirements of the fire authorities.
-
Comply with the accident prevention directives and the workplace directive.
-
The doors' swivel range must always be kept free.
-
Access to the housing by unauthorised persons must be prohibited.
-
The doors of the fire protection housing must be kept closed during
operation.
-
Secure the housing against tipping
Installation conditions of fire protection housings
-
The substrate must be level
-
Suitable solely for indoor installation
-
The installation site must be dry and free of frost, ambient tempe5 °C
to +30 °C
-
Not suitable for outdoor installation
-
The floor/wall must be suitable (load capacity, classification)
-
Carefully check the suitability of the wall properties with regard to the heavy
weight of the housing before installing the electrical hanging housing (FBxxLE
/ FBxxSE).
-
Check the suitability of the enclosed dowels with regard to the wall
properties.
-
Note the power loss of the installed devices and wiring in comparison with
the specified power loss of the distributor (VDE 0660, Part 500/504).
-
The housing must be aligned at its final installation site. The housing can be
lifted at its corners for this and its height compensated with spacers.
-
The housing must then stand horizontally.
-
The housing must be secured against tipping.
-
Check that the fire protection seals are undamaged.
-
Check that the door locks flawlessly when the housing is closed.
Содержание FB LE Series
Страница 1: ...Brandschutzgeh use Stand Wandmontage FBxxLE FBxxSE Montage und Bedienungsanleitung...
Страница 21: ...L fter Einheit anschlie en Technische nderungen vorbehalten 21 10 1 L fter Einheit Anschlussplan...
Страница 26: ...Befestigungssystem 26 Technische nderungen vorbehalten Einbauma e f r 1 feldigen Schrank...
Страница 27: ...Befestigungssystem Technische nderungen vorbehalten 27 Einbauma e f r 2 feldigen Schrank...
Страница 30: ...Fire Protection Enclosure FBxxLE FBxxSE Installation and Operation Instructions...
Страница 48: ...Ventilation diagram Technical changes reserved 19 Schematic diagram of the ventilation 9 Ventilation diagram...
Страница 50: ...Fan unit Connection Technical changes reserved 21 10 1 Fan unit Wiring diagram...
Страница 55: ...Fixing system 26 Technical changes reserved Assembly dimensions for 1 field enclosure...
Страница 56: ...Fixing system Technical changes reserved 27 Assembly dimensions for 2 field enclosure...