Single zone AOV User Manual
SETUP AND PROGRAMMING
32
Approved Document Ref: UI-SZAOV-01 Issue 2.01
OPTION 6 (Input LED and Detector LED) Change / Remove Keypad Access Code
The keypad can be used to activate the panel controls instead of using the key switch. The
default code is 1-2-3-4, however, this can be changed. It is also possible to disable the use of a
code entry to enable controls, forcing the use of the key switch only.
With the Input LED and Detector LED pulsing, start to enter the new four key code slowly and
deliberately, one number at a time, followed by ENTER.
If ENTER is pressed before the full code is entered or too many numbers are entered, the
operation is aborted and the current setting remains.
The General Fault (1), General Disablement (2), Test Mode (3) & Rain Status (4) LEDs will then
start to rapidly pulse in sequence to show the new code, after which time the panel will
automatically drop out of the set keypad entry mode.
Note: ‘Enable Controls’ codes must always start with a 1 or 2.
Changing the keypad code to 1 - 1 - 1 - 1 will disable the use of a keypad to enable controls.
When finished all the miscellaneous options programming, enter the next programming code or
disable the controls and return DIL switch 6 to ‘OFF’.
Input Circuit Function Settings
Input Circuit Function Settings
There are 3 functional settings available for each of the input circuits (Open, Close and Detector).
These are as follows:
•
Alarm latching - Normally a circuit latches an alarm input signal. This setting allows the
panel to clear automatically when the signal is removed. This is useful for interfacing
purposes.
•
Short circuit as alarm - For non-fault monitored systems. This allows a short circuit to
activate an alarm rather than a fault condition.
•
Detector removal monitoring (Detector circuit only) - The detector removal monitoring can
be turned off. For use with detectors which are not compatible with this function.
Enter the above code and press the ENTER button.
Use button 1 and 3 to move to the circuit that requires editing:
•
Open (Input LED and Vent Open LED lit),
•
Close (Input LED and Vent Closed LED lit),
•
Detector (Detector LED lit)